Certification
5.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
DC Power
Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
3
AC Power
Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Power
Ports
10 V
3
AC Power
Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
40 A/m continuous,
1000 A/m for 1 s
IEC
61000-4-8
Magnetic Field
Enclosure
Ports
1000 A/m for 1 s
5
DC Power
Ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC
61000-4-29
30% for 1 period,
60% for 50 periods
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
Ports
100% for 5 periods,
100% for 50 periods
Signal Ports
2 kV (Fail-Safe
Relay output)
DC Power
Ports
1.5 kV
Dielectric Strength
AC Power
Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power
Ports
5 kV
IEC 60255-5
HV Impulse
AC Power
Ports
5 kV
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RMC41 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
± 4 kV @ 2.5 kHz
Fast Transient
DC Power Ports
± 4 kV
24
RUGGEDCOM RMC41
Installation Manual, 04/2021, C79000-G8976-1010-11