Fuses, switches, wiring and earthing must be in compliance with local safety
regulations
Sensor cables should not be run parallel to mains-carrying cables powering
loads such as fans, actuators and pumps
The modules are designed for:
Mounting in a standard cabinet conforming to DIN 43 880
Wall mounting on an existing top hat rail (EN 50 022-35x7.5)
Wall mounting with 2 fixing screws
Flush panel mounting
Not permitted are wet or damp spaces; the permissible ambient temperatures
must be observed
Disconnected the system from power supply prior to mounting and installing the
module
The module insert must not be removed from the terminal base!
The module must be fitted on the right hand side of the Synco™ 700 control in
the correct order, in accordance with the internal configuration
The extension modules need not be wired, neither between themselves nor to
the Synco™ 700 control. The electrical connections are made automatically
when attaching the modules. If it is not possible to arrange all extension modules
side by side, the first of the detached modules must be connected to the previ-
ous module or the Synco™ 700 control by using the RMZ780 module connector.
In that case, the cumulated cable length must not exceed 10 meters
Low-voltage side
Mains voltage side
The connection terminals for protective extra low-voltage are located in the up-
per half of the module, those for mains voltage (actuators and pumps) at the bot-
tom
Only one solid or stranded wire may be connected to each terminal (spring cage
terminals). For fixing the wires, the cables must be stripped by 7 to 8 mm. To in-
troduce the wires into the spring cage terminals, or to remove them, a screw
driver size 0 or 1 is required. Cable strain relief can be ensured with the help of
the lugs for cable ties
The module mounted on a top hat rail together with other modules can only be
removed from the rail after the 3 catches have been brought into their release
and hold position (audible "click"). After removal, the catches must be pushed
back into their snap-on position
The module is supplied complete with Mounting Instructions
During the commissioning process, the outputs are in a defined off state.
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations..