Info pages boiler sequence manager
(Only with RMK770)
To go to the Info page:
1. Return to the start page by pressing the ESC button.
2. Press the INFO button.
3. Turn the OK knob until the required page appears.
State
On
= heat generation on
Off
= heat generation off
Cause
Here, the reason for the state of heat generation is
given. It should be considered that the boiler sequence
may be deactivated while the main pump is still running,
e.g. due to frost protection or overtemperature protec-
tion.
Main flow temperature
•
Actual value below the setpoint:
If the actual boiler temperature is lower than the set-
point for a longer period of time, additional boilers will
be released. The time of release depends especially
on the differential of these 2 values.
•
Actual value above the setpoint:
If the actual value remains above the setpoint for a
longer period of time, released boilers will be locked.
Return temperature
This is the temperature of the water returning to the
boiler from the consumers (heating circuit, DHW circuit).
Содержание RMH760B
Страница 2: ...Building Technologies HVAC Products CE1B3133x2 74 319 0560 0 a 10 10 2006 ...
Страница 36: ...34 Building Technologies HVAC Products CE1B3133x2 de 74 319 0560 0 a 10 10 2006 2006 Siemens Switzerland Ltd ...
Страница 70: ...34 Building Technologies HVAC Products CE1B3133x2 en 74 319 0560 0 a 10 10 2006 2006 Siemens Switzerland Ltd ...
Страница 104: ...34 Building Technologies HVAC Products CE1B3133x2 fr 74 319 0560 0 a 10 10 2006 2006 Siemens Switzerland Ltd ...
Страница 105: ...74 319 0560 0 B3133x2 Synco 700 nl Gebruiksaanwijzing Verwarmingsregelaar RMH760B Ketelvolgorderegelaar RMK770 ...
Страница 138: ...34 Building Technologies HVAC Products CE1B3133x2 nl 74 319 0560 0 a 10 10 2006 2006 Siemens Switzerland Ltd ...