The sequence of pulses issued by the control box identifies the possible types of malfunction, which are
listed in the table below.

 

SIGNAL

PROBABLE CAUSE

 

2 pulses

 

==

 

The flame does not stabilise at the end of the safety time:
– faulty ionisation probe;
– faulty or soiled gas valves;
– neutral/phase exchange;
– faulty ignition transformer
– poor burner regulation (insufficient gas).

3 pulses

 

===

 

Min. air pressure switch does not close:
– air pressure switch faulty;
– air pressure switch incorrectly regulated;
– max. air pressure switch triggered (if installed).

4 pulses

 

====

 

Min. air pressure switch does not open or light in the chamber before firing:
– air pressure switch faulty;
– air pressure switch incorrectly regulated.

7 pulses

 

=======

 

Loss of flame during operations:
– poor burner regulation (insufficient gas);
– faulty or soiled gas valves;
– short circuit between ionisation probe and earth.

10 pulses

 

=====

=====  

 

– Wiring error or internal fault.