67G Directional Earth Fault – Measured
Reference
Parameter
Value
θ
set
Characteristic angle setting
-95° to +95°
Vmin
set
Minimum voltage setting
0.33 to 3 V, Δ 0.5 V
CT/VT config
Van, Vbn, Vcn
Van, Vbn, Vcn
I
Applied current (for operate time)
0.1 ⋅ I
rated
1 ⋅ I
rated
V
Applied voltage
0.1 ⋅ V
rated
1 ⋅ V
rated
Operate Angle
Attribute
Value
θ
op
Characteristic angle (I with respect to V)
θ
set
, ± 5°
Operating angle
Forward
θ
set
- 85° ± 5° to θ
set
+ 85° ± 5°
Reverse
(θ
set
- 180°) - 85° ± 5° to (θ
set
- 180°) + 85 ° ± 5°
Variation in charac-
teristic angle
-10 °C to +55 °C
± 5 °
f
rated
± 5 %
± 5 °
Operate Threshold
Attribute
Value
Minimum operating voltage
> 0.33 V ± 0.25 V
Operate and Reset Time
Attribute
Value
t
op
Operate time
Typically 32 ms
< 40 ms at characteristic angle + 50/51 element operate time
t
reset
Reset time
Typically < 65 ms at characteristic angle
10.25
Technical Data
10.25 67G Directional Earth Fault – Measured
492
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...