General Device Data
Instrumentation
Instrument Value
Reference
Typical Accuracy
I
Current
10 % to 200 % I
rated
± 1 % or ± 1 % I
rated
V
Voltage
10 % to 200 % V
rated
± 1 % or ± 1 % V
rated
W
Power (P)
V = V
rated
I = 10 % to 200 % I
rated
PF ≥ 0.8
± 3 % S
rated
where S
rated
= V
rated
⋅ I
rated
VA
r
Reactive power (Q)
VA
Apparent power (S)
PF
Power factor
V = V
rated
, 10 % to 200 % I
rated
, PF ≥ 0.8
± 0.05
f
Frequency
47.5 to 52.5 Hz @ 50 Hz
57 to 63 Hz @ 60 Hz
± 10 mHz