Parameter:
Setting
•
Default setting: 0.2 x I
n
(0.2 I
rated
)
The setting to be appropriate to the respective application.
A pickup value of 10 % is a practicable value for fault indications of electrical machines.
Parameter:
Delay
•
Default setting:
0 s
No specific recommendation is given: The setting to be appropriate to the respective application.
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
37 Undercurrent
Enabled
Disabled
Disabled
Functions > Protection > 37 > Gn 37G-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.005 to 5 I
rated
, Δ 0.001 I
rated
0.2 ⋅
I
rated
Delay
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
IEC 61850 Functional Information Mapping
A37GPTUC*.Mod
Information
37G Undercurrent Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A37GPTUC*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
5.6.5
5.6.6
Protection and Automation Functions
5.6 37G Undercurrent Earth Fault – Measured
178
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...