27 Undervoltage Protection – 3-Phase
Overview of Function
3 phase undervoltage protection is used to:
•
Monitor the permissible voltage range and provide alarms for values below normal limits.
•
Decouple or reconfigure changeover systems when loss of supply is detected.
•
To selectively disconnect loads (load shedding) to match generation capacity following a loss of genera-
tion which can be detected by undervoltage.
Undervoltages are typically caused by loss of generation, overload of lines or removal of lines from service,
voltage controller failure at the transformer and error during control operations.
Structure of the Function
The 3 phase undervoltage function has group dependent settings. These settings can be different in each
settings group – group numbers (Gn) 1 to 4.
This function corresponds to the logical node
A27PTUV*
in IEC 61850.
The function monitors the primary system using the 3 phase voltage inputs e.g. VT1/2/3. The fundamental
frequency component is measured from processing of the measured voltage samples.
•
A definite time delayed operate characteristic is used. Settings are provided for operate (pickup)
threshold voltage, reset voltage level (hysteresis/drop-off) and time delay.
•
Outputs are provided for pickup and operation.
5.3
5.3.1
5.3.2
Protection and Automation Functions
5.3 27 Undervoltage Protection – 3-Phase
158
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...