Siemens REP-1 Скачать руководство пользователя страница 2

2

Basic Repeater Operation

(Refer to Figures 2A and 2B)

The REP-1 has two independent 2-wire
RS-485 repeaters that permit the addition
of another 80 ohms of wire to a Style 4
circuit by using the REP-1 at the end of the
network. When an REP-1 Repeater is in
place, there can be up to 64 nodes on that
network; however, two of the nodes are
used for the repeater module itself.

An REP-1 module uses one node on each
network pair to which it is connected. Al-
though this decreases the 32 available
nodes on a network run, the REP-1 module
adds 31 new nodes on the repeated net-
work.

The REP-1 module occupies one node on
the original network and one node on the
repeated network in both Style 4 and Style
7 wiring.

Adding a T-Tap to a System

(See Figures 2C and 2D)

I

f an REP-1 module is connected along a

Style 4 or a Style 7 network, the repeated
network can run in a new direction. This
type of setup makes it possible to have a
star configuration on the network.

Converting Style 7  to Style 4 in
a System

(See Figure 2E)

A Style 4 tap can be added to a Style 7
network by using an REP-1 module. This
is helpful when installing RCC-1s and
MOI-1s/7s in a Style 7 system if Style 7 is
not required for those modules.

When an REP-1 is used to add Style 4 to  a
Style 7 network, REP-1 connects to two
nodes, thus adding 30 new nodes.

CSG-M Control of System Size

Even though the REP-1 supplies an
increased node count in a system, the total
system size is still controlled by the CSG-M.
This limit guarantees that the MXL System
can support the number of modules installed.

PROGRAMMING

(See Figure 1)

There is one switch (S1) and one jumper
(JP1) on the REP-1 that must be set before
installing the REP-1 in the MOM-4 module.

Setting the Switch on REP-1

The S1 switch on the REP-1 has two
positions available.

The

 left-side position

 

(7 to 4)

 of the

switch enables conversion from
Style 7 to Style 4.

Select the 

right-side position

(NORM)

 of the switch if the REP-1

is used as a repeater.

Selecting the Correct Position
for the JP1 Jumper

The REP-1 provides electrical isolation
between the local power supply and the
RS-485 lines. The JP1 jumper on the
REP-1 has two positions relating to this
feature—

PSR 

and 

MMB.

Select the 

left-side position

 

(PSR)

 for

the jumper if the REP-1 is installed in
an enclosure with a PSR-1. This set-
ting protects ground fault isolation for
the system. (See 

CAUTION 

on the next

page.)

Select the 

right-side position

 

(MMB)

for the jumper if the REP-1 is installed
in an enclosure with an MMB so as
to protect ground fault isolation circuits

.

For additional information on the MXL/MXLV
System, refer to the 

MXL/MXLV Manual,

P/N 315-092036.

Содержание REP-1

Страница 1: ...ew terminals of an MXL System module The REP 1 module reproduces the RS 485 signal on a new pair of wires The new signal makes it possible to add more nodes to the system OPERATION An REP 1 Repeater module may be used to Installation Instructions Model REP 1 Network Repeater Module Figure 1 REP 1 Repeater PC Board 1 Add nodes to the end of a system network by providing a repeated network 2 Add a S...

Страница 2: ...REP 1 is used to add Style 4 to a Style 7 network REP 1 connects to two nodes thus adding 30 new nodes CSG M Control of System Size Even though the REP 1 supplies an increased node count in a system the total system size is still controlled by the CSG M This limit guarantees that the MXL System can support the number of modules installed PROGRAMMING See Figure 1 There is one switch S1 and one jump...

Страница 3: ...o Directions with Style 4 C T Tap Running in One Direction with Style 4 A Basic Repeater Style 4 t n e r r u C e l u d o M C D V 5 e v i t c A A m 0 t n e r r u C e l u d o M C D V 4 2 e v i t c A A m 0 4 t n e r r u C e l u d o M C D V 4 2 y b d n a t S A m 0 4 CAUTION For NIM 1R Network If a REP 1 is used on a NIM 1R network place the JP1 jumper in the PSR position no matter in which type of cab...

Страница 4: ...card guides and firmly seat ing it in the card edge connector Checking Limits Do not connect more than two REP 1s in series for proper operation of the network To be sure there are no more than two REP 1s in series check that 1 There are no more than two REP 1s between any MXL module and the MMB or 2 In an NIM 1R network there are no more than two REP 1s between any pair of NIM 1Rs in the network ...

Страница 5: ...he REP 1 is not used in this configuration so it has both sides terminated as shown For Style 7 networks Figure 4 use both halves of the REP 1 Figure 4 Basic Repeater Style 7 Notes 1 Use 18 AWG minimum wire 2 Limit maximum resistance per pair to 80 ohms 3 Use shielded twisted pair 4 Terminate the shield ONLY at the MMB enclosure 5 The wiring is power limited according to NFPA 70 per NEC 760 6 Maxi...

Страница 6: ... a Style 7 network Figure 6 shows a Style 4 tap that begins at the REP 1 This tap can also be run in two directions if the end of line resistors are connected to the ends of the Style 4 tap A typical use of this connection to either an RCC 1 1F or MOI 7 would be for a group of annunciators where Style 7 wiring is not required for the annun ciators but the rest of the system must be Style 7 Do not ...

Страница 7: ...enclosure 5 The wiring is power limited according to NFPA 70 per NEC 760 6 Maximum voltage is 8V P P 7 Maximum current is 150mA 8 Use the end of line resistor P N 140 820150 120 ohms 1 4W See Figure 2E for further information 9 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information CONNECT ONLY TO RCC 1 1F OR MOI 7 ...

Страница 8: ...P N 315 092686 8 Siemens Industry Inc BuildingTechnologies Division Florham Park NJ Siemens BuildingTechnologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: