The Model REP-1 from Siemens Industry,
Inc., is an MXL module that permits the
user to extend the distance of the MXL
RS-485 network as well as the distance of
the NIM-1R RS-485 network. The REP-1
also supports both Style 4 and Style 7
wiring.
The MXL network uses an RS-485 inter-
face for its network wiring. The RS-485
supports up to 32 nodes on each pair of
wires (See
Note
below).
P/N 315-092686-8
Note:
A node is any location where
the network wires are con-
nected to the screw terminals
of an MXL System module.
The REP-1 module reproduces the RS-485
signal on a new pair of wires. The new
signal makes it possible to add more nodes
to the system.
OPERATION
An REP-1 Repeater module may be used to:
Installation Instructions
Model REP-1
Network Repeater Module
Figure 1
REP-1 Repeater PC Board
1. Add nodes to the end of a system
network by providing a repeated
network,
2. Add a Style 4 or Style 7 tap to a
system, or
3. Add a Style 4 tap to a Style 7
network.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
INTRODUCTION