Document No. 129-905 
Installation Instructions 
March 26, 2015 
 

Page 2 of 18

 

Siemens Industry, Inc.

 

NOTE: 

Ensure that the UP arrows embossed 
on the base plate are pointed upward. 

 

Figure 2.  Thermostat Base Plate. 

NOTE: 

If 24 Vac was verified as being present 
at the thermostat wires (see 

Prerequisites

), skip Step 2 and proceed 

to Step 3. 

2.  If 24 Vac is not present at the thermostat: 

a.  Locate the 24 Vac transformer or 24 Vac on 

the terminal strip on the HVAC unit. Attach a 
thermostat wire to the 24 Vac source. See 
the HVAC equipment schematics to verify 
the correct terminals. 

b.  Attach the other end of the unused wire to 

the thermostat RH or RC terminal. 

c.  Verify that 24 Vac is present between the 

RH/RC and C terminals. 

3. 

Attach the existing wires to the appropriate 
terminals on the thermostat base plate. See 

Wiring Diagrams

, Figure 4 and Figure 5. 

Optional:

 If using Auxiliary Inputs 1 to 4 or 

configurable outputs 1 to 3, use setup 
parameters P301 to P320 to set functionality. 

4. 

For systems with dual transformers, do the 
following; otherwise, proceed to Step 5: 

If separate transformers are used for heating 
and cooling systems, connect 24 Vac from the 
cooling system to RC, and 24 Vac from the 
heating system to RH. Remove Jumper RH-
RC. 

Optional:

 Auxiliary Output 3 can be changed to 

a dry (unpowered) contact by removing Jumper 
RC-C3 See 

Wiring Diagrams

, Figure 6. 

5. 

Attach thermostat to the base plate by engaging 
tabs at the top and rotating the thermostat 
downward until it is securely seated on the base 
plate. 

6. 

Secure the thermostat to the base plate with the 
Phillips screws (provided), using the holes at 
the bottom of the housing. 

The installation is now complete. Restore power, 
and continue to 

Thermostat Setup

Thermostat Setup 

 

Figure 3.  Thermostat Display. 

Thermostat Display 

Navigation Bar 

Only one function can be selected at a time. The 
small bar (cursor) below the function icon indicates 
that a function is selected. Pressing an icon twice 
navigates back to the Main screen. 

A double bar cursor below the 

Settings icon

 [

indicates that you are in Programming mode. 

The navigation bar at the bottom of the display 
consists of four function icons.  

Table 1.  Navigation Bar Icons. 

Icon 

Name 

Purpose 

 

Setpoint 

Enables adustment of temperature 
and humidity (if applicable) 
setpoints. Unit will display heating 
setpoint if in Heating mode or 
cooling setpoint if in Cooling mode.  

 

Fan 

Control 

Enables fan relay to be controlled 
as needed by thermostat (AUTO) or 
to be on continuously (ON).  

 

Mode 

Selector 

Enables manual changeover 
between Heating and Cooling 
mode. AUTO will enable the 
thermostat to automatically switch 
between heating and cooling mode 
as required. OFF will disable all 
control functions. 

 

Settings 

Enables Scheduler, Time/Date, and 
Installer Set Up configuration. Also 
enables access to service reminder 
and fault messages. 

 

Содержание RDY2000

Страница 1: ...ss of data may occur if you do not follow the procedures as specified Required Tools No 1 Phillips screwdriver 1 8 flat blade screwdriver Drill with 1 8 drill bit Expected Installation Time 15 minutes CAUTION The RDY2000 is an advanced controller designed to be installed by professional HVAC technicians Installation by non qualified personnel may result in degraded system efficiency occupant disco...

Страница 2: ...ving Jumper RC C3 See Wiring Diagrams Figure 6 5 Attach thermostat to the base plate by engaging tabs at the top and rotating the thermostat downward until it is securely seated on the base plate 6 Secure the thermostat to the base plate with the Phillips screws provided using the holes at the bottom of the housing The installation is now complete Restore power and continue to Thermostat Setup The...

Страница 3: ...ion relay is on Cool Mode The system is actively in cooling mode Heat Mode The system is actively in heating mode Heating Cooling Stages Each segment represents one stage of heating or cooling Auxiliary Heating Auxiliary heating stage AUX Stage 1 Aux 2 Stage 2 Service Reminders and Fault Messages Service reminders appear at the right side of the screen SERVICE UV LAMP SERVICE HUMIDIFIER SERVICE AI...

Страница 4: ...Document No 129 905 Installation Instructions March 26 2015 Page 4 of 18 Siemens Industry Inc Wiring Diagrams Figure 4 Wiring Schematic Conventional System ...

Страница 5: ...Document No 129 905 Installation Instructions March 26 2015 Siemens Industry Inc Page 5 of 18 Figure 5 Wiring Schematic Heat Pump Figure 6 Wiring Schematic Aux Output 3 ...

Страница 6: ...can be modified For instance if the thermostat is in heating mode only the heating setpoint displays and can be modified If the thermostat is in AUTO mode both the heating and cooling setpoints will be displayed and can be modified 3 Use the left and right arrows to access the different setpoints and the and icons to adjust the setpoints 4 Touch the center of the screen to exit Setpoint Programmin...

Страница 7: ...the screen is locked To unlock the keypad do the following 1 Touch the center of the Home screen to access the room temperature screen 2 Press the Settings icon once and LOCKED displays 3 Press and hold the Settings icon for 5 seconds PASSWORD displays 4 Using the lower left and right arrows enter the INSTALLER password 5 Press PASSWORD to accept the password 6 Set Parameter 211 Keypad Lockout to ...

Страница 8: ... 1 2 3 7 2 0 Disable Scheduler 1 Schedule all days with same schedule 2 One schedule for M F and another for Sat Sun 3 One schedule for M F Sat Sun scheduled individually 7 Schedule each day individually See Table 9 through Table 13 P108 Program Periods PERIODS 2 4 2 Sets number of program periods per day 2 2 periods Day Night 4 4 periods Wake Day Evng Night This parameter only appears if P107 0 P...

Страница 9: ...5 F 7 0 C OFF Heat pump compressor will not operate below this outdoor temp forcing unit to auxiliary heat An outdoor temperature sensor is required NOTE If P206 OFF set P508 1 F 0 5 C This parameter only appears for the following conditions P101 HP P104 0 P105 YES P301 P305 P309 or P313 5 P206 P207 P207 Heat Pump Auxiliary Heat Lockout HP AUX LO OFF 40 F 4 0 C 45 F 7 0 C 50 F 10 0 C 55 F 13 0 C 6...

Страница 10: ...9 0 0 Not Used 1 Indoor Temperature Remote 2 Indoor Temperature Average 3 Supply Temp 4 Return Temp 5 Outdoor Temp 6 Humidity 0 10V 7 CO2 0 10V 8 Occupancy DI 9 Fault Selections for Inputs 1 4 cannot be duplicated If set to 9 fault a DI causes SERVICE REQUIRED segment to activate See Table 14 for a list of optional sensors approved for use with the RDY2000 P306 Temperature Input 2 Type TMP IN 2 0 ...

Страница 11: ... 0V 40 F 4 4 C Only appears if P314 1 P315 P316 P316 Temperature Input 4 High TMP 4 HI P315 value to 250 F 120 0 C 120 F 50 0 C Calibrates thermostat to high end of temp sensor signal at 10 volts for example 10V 250 F 121 1 C Only appears if P314 1 P316 P315 P317 Aux Output 1 OUT1 AUX OUT 1 0 1 2 3 4 5 0 0 Not Used 1 Humidification 2 Dehumidification 3 Occupied 4 Air Quality 5 Economizer Enable Se...

Страница 12: ...If Installer Password is changed a new password should be recorded for future reference P701 Firmware Revision FIRMWARE X X N A Read Only Expert Level Menus 1 Touch the center of the Home screen 2 Press the Settings icon SCHEDULER displays 3 Press the left arrow 4 Press INSTALLER 5 Using the lower left and right arrows enter the password 6 Press PASSWORD to accept the password and return the unit ...

Страница 13: ...in minutes before system will automatically switch from heating to cooling or vice versa P506 Cooling Deadband CL DEADBND 1 F 0 5 C to 5 F 4 0 C 1 F The deadband is divided equally above and below setpoint Cooling will begin when temperature exceeds upper point of deadband and ceases when temperature falls below lower point of deadband P507 Stage Delay Heating STG DLY HT 1 to 10 minutes 2 Time del...

Страница 14: ...gized ON Relay energized P907 Test Output 1 OUT1 TST ON OFF OFF OFF Relay not energized ON Relay energized P908 Test Output 2 OUT2 TST ON OFF OFF OFF Relay not energized ON Relay energized P909 Test Output 3 OUT3 TST ON OFF OFF OFF Relay not energized ON Relay energized P911 Expert Password XPRT PW 50 00 to 99 99 99 99 Auxiliary Sequences The RDY2000 primary sequences are designed to control singl...

Страница 15: ...ires a schedule to be configured Occupancy Notification Parameters P301 P305 P309 P313 If the optional occupancy sensor is used one of these must be set to 8 P317 P318 P319 To signal an external device that the space is occupied one of these must be set to 3 P404 If the optional occupancy sensor is used P404 can be used to set a minimum run timer for any actions that are activated by occupancy suc...

Страница 16: ...y Evng Night Setpoint Heat F 70 62 70 62 70 68 70 62 70 68 70 62 Setpoint Cool F 75 82 75 82 75 78 75 82 75 78 75 82 Time 6 00 AM 10 00 PM 8 00 AM 10 00 PM 6 00 AM 11 00 AM 1 00 PM 10 00 PM 8 00 AM 11 00 AM 1 00 PM 10 00 PM Table 11 Work Week Schedule with Separate Weekend Days 2 Periods per Day Day Work Week Monday Friday Saturday Sunday Phase Day Night Day Night Day Night Setpoint Heat F 70 62 7...

Страница 17: ...lass B digital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee tha...

Страница 18: ...erature Input 2 Type 0 P307 Temperature Input 2 Low 0 F 18 0 C P308 Temperature Input 2 High 120 F 50 0 C P309 Configurable Input 3 IN3 0 P310 Temperature Input 3 Type 0 P311 Temperature Input 3 Low 0 F 18 0 C P312 Temperature Input 3 High 120 F 50 0 C P313 Configurable Input 4 IN4 0 P314 Temperature Input 4 Type 0 P315 Temperature Input 4 Low 0 F 18 0 C P316 Temperature Input 4 High 120 F 50 0 C ...

Отзывы: