3 / 12 

Siemens 

Semi-flush-mount Room Thermostats with LCD 

CB1N3064en 

Building Technologies 

 

24.08.2010 

kept running all the time (e.g. in apartments or shops during unoccupied periods), 
when setting parameter P21 

ON in dead zone

. In this case, the fan keeps running 

at minimum fan speed 1. 

Control sequences 

Used in conjunction with a valve, either for heating/cooling with changeover, heat-
ing only or cooling only. 

Used in conjunction with a 1-stage compressor for cooling only or heating only. 

Heating mode 

Cooling mode 

 

 

T[

°

C] 

Room temperature 

SDH 

Switching differential 

Heating

 

Room temperature setpoint 

SDC 

Switching differential 

Cooling

 

Y11 

Control output 

Valve

 or 

Compressor

 

 

 
The valve or compressor receives 

OPEN

 command via control output Y11 when: 

  the acquired room temperature lies by half the switching differential below the 

setpoint (heating mode) or above the setpoint (cooling mode), and 

  control output Y11 was not energized for more than 1 minute (the 

Minimum 

output off time

 is a fix value) 

The valve or compressor receives 

CLOSE

 command via control output Y11 when: 

  the acquired room temperature lies by half the switching differential above the 

setpoint (heating mode) or below the setpoint (cooling mode), and 

  control output Y11 was energized for more than 1 minute (the 

Minimum output 

on time

 is a fix value) 

Control output Y12 delivers a control command which is inverted to the control 
command at output Y11 and which can be used for open valves normally. 

When pressing the Heat/Cool mode selector, the controller will change from heat-
ing to cooling, or vice versa. 
If the controller is set to 

Cooling only

 or 

Heating only

,

 changeover will not be 

possible. Only the corresponding mode can be selected by the Heat/Cool mode 
selector (parameter P22, factory setting is 

manual changeover

). 

The minimum output on/off time of Y11 and Y12 fixed at 1 minute. It means that 
any readjustment of the setpoint or of Heat/Cool mode changeover will be hold for 
1 minute before Y11 and Y12 react. 

Fan operation 

The fan operates either in automatic mode or at the selected speed when using 
manual mode. In automatic mode, the fan speed depends on the setpoint and the 
current room temperature. When the room temperature reaches the setpoint, the 
control valve will close and the fan either remains in fan speed 1 or switches off 
(parameter P21, factory setting: ON in dead zone). 
In 

Temperature-dependent

 fan control the fan switches off (see diagram below). 

The individual switching differentials of the fan speed 1 (Q1 only) can be adjusted 

Water-based fan coil 
application 

Compressor based 
application 

ON 

OFF 

Notes:

 

Heat/Cool mode 

Minimum output 
on/off time Y11, Y12 

Содержание RDF510.2

Страница 1: ...l Automatic or manual Manual heating cooling changeover or continuous Cooling only or Heating only Operating modes Comfort Protection Adjustable commissioning and control parameters Optional display of room temperature or setpoint Minimum and maximum setpoint limitation Display temperature in increments of 0 5 C or 1 F Operating voltage AC 230 V Mounting on recessed rectangular conduit box with fi...

Страница 2: ...mode adjust able via parameters P08 and P09 The display can show current room temperature or the setpoint adjusted by user This can be selected via parameter P18 factory setting is the current room tem perature The heating and cooling symbols on the display show the status of the fan coil This means that the symbols are also shown while the controller operates in the dead zone If required room tem...

Страница 3: ...output Y11 was energized for more than 1 minute the Minimum output on time is a fix value Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for open valves normally When pressing the Heat Cool mode selector the controller will change from heat ing to cooling or vice versa If the controller is set to Cooling only or Heating on...

Страница 4: ...fan motor starts to overcome inertia and friction Error handling When the room temperature is out of the measuring range which means above 49 C or below 0 C the display shows the limiting temperature in flashing figures 0 C or 49 C If the current setpoint is not OFF see parameters P03 and the controller is in heating mode when the temperature is below 0 C output Y11 will be energized In all other ...

Страница 5: ...ill show 888 during the reloading process Para meter Meaning Setting range Factory setting P03 Setpoint of heating in Protection Mode WheatStb OFF 5 C WcoolStb 8 C P04 Setpoint of cooling in Protection Mode WcoolStb OFF WheatStb 40 C OFF P05 Minimum setpoint limitation in Comfort Mode WminComf 5 C WmaxComf 5 C P06 Maximum setpoint limitation in Comfort Mode WmaxComf WminComf 40 C 35 C P07 Sensor c...

Страница 6: ...21 N4863 N4863AP Thermal actuator for radiator valves small valves and zone valves STA21 N4877 Thermal actuator for terminal unit valves STP21 N4878 Electric actuator for zone valves SUA N4832 Conduit box for semi flush mount thermostat ARG71 S55770 T137 N3009 Only available in AP UAE SA and IN Ordering When ordering please indicate the product name product number and SSN num ber Room Thermostat R...

Страница 7: ...parameters Symbol used when displaying the current room temperature Fan mode and fan speed indicator Automatic fan active Manual fan active Fan mode button changing the fan mode Auto manual changing the fan speed Low Medium High Heat Cool mode selector For the changeover between cooling mode and heating mode if P22 3 Or Operating mode button For the selection of comfort mode and protection mode Or...

Страница 8: ...egments displayed indicating that the reset has been correctly made This takes about 3 seconds Then the controller is ready for commissioning by qualified HVAC staff The control parameters of the controller can be set to ensure optimum performance of the entire system please refer to Parameter Settings Depending on the application the Heat Cool mode must be set via parameter P22 Factory setting is...

Страница 9: ...oling mode 20 C 8 C OFF Built in room temperature sensor Measuring range Accuracy at 25 C Temperature calibration range 0 49 C 0 5 K 3 K Resolution of settings and display Setpoints Current temperature value displayed 0 5 C 0 5 C Operation Climatic conditions Temperature Humidity to IEC 721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC ...

Страница 10: ...gree of protection of housing IP 30 as per EN 60529 Connection terminals solid wires or prepared stranded wires 2 x 0 4 1 5 mm 2 or 1 x 0 4 2 5 mm 2 Weight 0 17 kg Color of housing front white RAL 9003 Connection terminals L N Operating voltage AC 230 V Q1 Control output Fan speed 1 AC 230 V Q2 Control output Fan speed 2 AC 230 V Q3 Control output Fan speed 3 AC 230 V Y11 Control output Valve AC 2...

Страница 11: ...11 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 Dimensions ...

Страница 12: ...12 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 2010 Siemens Schweiz AG Subject to change ...

Отзывы: