CE1B3076.2en / 25 Feb 2010                                                                                                                                                                         Subject to change                                                                                                                                                  Siemens Building Technologies

 

Setting time of day and weekday 

 

 

 

+ – 

 24h 

 12 h 

 
   

 

 + – 

   

1. Keep the   button pressed until the time digits start to flash.  

Press 

+

 or 

 to set the time of day. 

If the current

 

time is in 24-hour format and you wish to change to the 12-hour format, 

press 

+

 passing 23:59 or press 

 passing 00:00.  

Back to 24-hour format: same procedure with 11.59 PM. 

2.  Confirm the time of day by pressing   and the weekday indicator starts to flash. 
3. Press 

+

 or 

– 

to set the current weekday. 

4.  Confirm the current weekday by pressing  . 

Set time schedules  

 

 

 

 Ax

 

   

 

 + – 

 

 + – 

 

 

 

 + – 

   

 

To adjust the time schedule, keep the 

 button pressed for 3 seconds to go to the timer 

setting mode.  
This mode is indicated by displaying 

Ax

 (x= auto timer 1...8) and the time flashing.  

For each timer, proceed as follows: 
1.

 

The 

 and   symbols are displayed. Press 

+

 or 

 to adjust the comfort mode start 

time and confirm by pressing  . 

2.

 

The 

 and   symbols are displayed. Press 

+

 or 

 to adjust the comfort mode end 

time / energy saving start time and confirm by pressing  . 

3.

 

Symbol 

 will flash. Press 

+

 or 

 to select or deselect each day and advance to the 

next day.  

4.

 

Press   to confirm the settings for the actual timer and advance to the next timer. 

The thermostat will leave the timer setting mode if no button is pressed within 20 
seconds. All changes made after the last press of the   button will not be saved. 

View the timer settings  

 

 

Press the 

 button to sequentially review the 8 auto timers. 

Reload default timer settings  

   
 

+ – /  

 

1.  Set the thermostat to protection mode  . 
2. Press 

+

 and 

 simultaneously for 3 seconds. Release and, within 2 seconds, press 

2 times 

 

Days 

Thermostat is in Comfort mode   

Mo (1) – Fr (5) 

6:30 – 8:30 (A1) 

17:30 – 22:30 (A2) 

Sa (6) 

8:00 – 23:00 (A3) 

Su (7) 

8:00 – 22:30 (A4) 

 

Default 

settings 

 

 – In the remaining time thermostat is in energy saving mode. 
 – Timers A5…A8 are free, no default settings. 

Button lock  

 

 

 
 
 
 

 

Press operating mode button   for 5 seconds to lock or unlock the buttons if manual 
button lock is configured (parameter P14 = 2).  
The thermostat automatically locks the buttons 30 seconds after the last adjustment if 
"Auto lock" is configured (P14 = 1). 
The key symbol 

 indicates locked buttons.  

Reminder to clean filters and for external faults 

      FIL 

 
 

This message reminds you to clean your HVAC equipment filters. 
It is displayed after 

………… “fan operating hours” and disappears when the thermostat 

is set to Protection (   ). 

 

* Needs to be configured by your HVAC installer

 

Note: Energy saving mode 

 

 

The energy saving setpoints are factory-set to 15 °C for heating and 30 °C for cooling.  
Use parameters P11 and P12 to adjust the values. 

Important

:

 

You can set these setpoints to 

OFF

; the thermostat then is inactive,

 

i.e. no protective heating or cooling function. 

 Risk of frost!

 

Commissioning 

You can adjust a number of control parameters to adapt the thermostat to your system and optimize control performance. You can do this during 
operation via the buttons on the thermostat. 

Control parameters 

Proceed as follows to change the most important control parameters: 
(Your HVAC installer can set additional parameters) 

 

+ / – 
 

1. Press 

the 

 and 

+

 buttons simultaneously at least 3 seconds.  

Release, and within 2 seconds, press 

+

 again for 3 seconds. "P01" is displayed. 

2.  Repeatedly press the 

+

 or 

 button to select the required parameter. 

P01

P02

P08

P14

+

-

+

-

-

+

3171z99

End

-

+

-

P13

+

-

 

3. Press 

+

 and 

 simultaneously. The current value of the selected parameter begins to flash, allowing you to change the value by 

repeatedly pressing 

+

 or 

4.  The next parameter is displayed when you press 

+

 and 

 again simultaneously. 

5.  Repeat steps 2 to 4 to display and change additional parameters. 
6. Press 

+

 or 

 until “End” is displayed, and then press 

+

 and 

 simultaneously to save the change and exit parameter entry mode.  

10 seconds after the last display or setting, all changes are saved and the thermostat will leave parameter setting mode. 

 

Para-
meter 

Description 

Factory setting 

Setting range  

Adj 

 

P01 Control 

sequence 

 

2-pipe

…: [0…3] 

1 (Cooling only) 

 

4-pipe:.   

 [2…4] 

4 (Heating & cooling) 

0 = Heating only 

1 = Cooling only 

2 = Manual heating or cooling 

3 = Auto changeover 

4 = Heating & cooling 

 

P02 

Mode selection by user via operating mode button   

1 (Comfort, 

 Protection) 

1 = Comfort, Protection 

2 = Comfort, Energy Saving, 

Protection 

 

P04 

Selection of °C or °F 

°C 

0 = °C  

1 = °F 

 

P05 Sensor 

calibration 

0.0 °C 

– 3 ... +3 °C  

 

P06 

Standard temperature display 

0 (Room temp.) 

0 = Room temperature 

1 = Setpoint 

 

P08 

Comfort basic setpoint 

21 °C 

5 ... 40 °C 

 

P09 

Minimum setpoint limitation in Comfort 

(Wmin

Comf

  5 °C 

5 ... 40 °C 

 

P10 

Maximum setpoint limitation in Comfort 

(Wmax

Comf

35 °C 

5 ... 40 °C 

 

P11 

Setpoint of heating in Energy Saving  

(Wheat

Eco

15 °C 

OFF, 5 °C…Wcool

Eco

 

 

P12 

Setpoint of cooling in Energy Saving 

(Wcool

Eco

30 °C  

OFF, Wheat

Eco

…40°C  

P13 *** Electrical heater in cooling mode 

ON 

OFF = disabled  

ON   = enabled 

 

P14 Button 

lock 

(Press operating mode button   for 7 seconds to lock or unlock 

the buttons) 

0 (Disabled) 

0 = Disabled 

1 = Auto lock 

2 = Manual lock 

 

 
 

 

 

*** Parameter P13 is only displayed for application "2-pipe with el heater". 
All temperature settings in increments of 0.5 °C. 

 

 Please record all changes you make! 

 