26
Application
How to set the application
VAV single duct, cooling only
– Damper actuator: 0…10 V
– Window contact
1. Thermostat:
RDG400
2. DIP switch:
Application single duct
Y10 = DC 0...10 V
3. Wire:
Actuator
→
Y10-Go-G
Window contact
→
D1-GND
4. Parameters:
no change (= default)
TIPS
– Window contact for saving energy during airing the rooms
VAV single duct and el. reheater
– Damper actuator: 3-pos
– El. heater: DC 0...10V
– Central time switch
1. Thermostat:
RDG400
2. DIP switch:
Application single duct +
el. heater
Y10 = DC 0...10 V
3. Wire:
Actuator
→
Y1/Y2-Go
El. heater
→
Y10-Go
Time switch
→
D1-GND
4. Parameters:
P47 = 1 (VAV output 3-pt)
TIPS
– Use a central time switch (e.g. SEH62.1) to set back room
temperature during non-business hours
– Adjust parameter prolong comfort period (P68) to allow
occupant to override the central time switch, e.g. by working
overtime
Compressor with reverse valve
– Compressor: ON/OFF
– Reverse valve: ON/OFF
1. Thermostat:
RDG110
2. DIP switch:
Application 4-pipe
3. Wire:
Compressor
→
Y11/Y21-N
RV
→
Y12/Y22-N
4. Parameters:
P52 = 0 (Fan disable)
– Set control sequence to manual change over (P01=2);
then the user can select manually between heating or cooling
VAV application examples