Operating Instructions

CB1B1425en_01 / 2014-11-26

Siemens Building Technologies

Does symbol

appear on the display?

Symbol

 is displayed when the batteries are low.

Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:

·

  Get 2 new alkaline batteries type AAA

·

  Remove the battery holder and then the batteries.

Insert the new batteries and, within 1.5 minutes,
replace the battery holder

·

  Ensure the exhausted batteries are disposed of

correctly, in compliance with environm ental
requirements

Do you want to lock the keypad?

Mode

Press and hold

 Mode

 for at least 7 seconds to

activate a button lock. Repeat to unlock.

The unit operates normally when the buttons
are locked, but changes cannot be made.

Receiver’s LED indication

State of receiver

State of LED

Power up (or reset) 

The red and green LEDs flash
alternately for 5 seconds, then
change to constantly red.

Note: If the receiver was previ-
ously programmed, it shows
immediately constantly red.

Learning mode

Successful learning
mode

The red and green LEDs flash
alternatively.

If RCR100RF learning is
successful, the green LED will
flash for 10 minutes.

Signal ok and
output status
change

The green LED is constantly lit,
and if the output status
changes, the green LED flashes
for 3 seconds, then changes
back to constantly green.

Fail to receive
wireless data

If the RCR100RF fails to receive
wireless data, the red LED will
start to flash after 125 minutes.

If the RCR100RF signal is
recovered, it will return to the
previous LED state.

Do you want to change parameters?

+

Ok
Mode

If you want to change control parameters,
proceed as follows:

·

 Press

+

and

simultaneously for 5

seconds

·

  Release the buttons and parameter

P01 is displayed on the bottom
segment

·

 Press

+

or

to scroll to the parameter

that needs to be changed

·

 Press

Ok

to select the parameter

·

 Press

+

or

to change the value

·

 Press

Ok

to confirm the changed value

·

 Press

Mode

 to exit the parameters

without saving or wait for the program
to exit automatically

Parameter list

Parameter
no.

Description

Setting range
(default)

P01

Time format

1 = 24:00 hours
(default)
2 = 12:00 am/pm

P02

Selection of °C or
°F

1 = °C (default)
2 = °F

P03

Standard
temperature display

1 = room temperature
(default)
2 = setpoint

P04

Temperature
sensor calibration

-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C

P06

Comfort setpoint
lock

0 = OFF (default)
1 = ON

à

 locked

according to setting
in permanent
temperature setpoint

P08

Economy setpoint
lock

0 = OFF (default)
1 = ON

à

 locked

according to setting
in permanent
temperature setpoint

P09

Buzzer

0 = OFF
1 = ON (default)

P10

Show frost
protection icon

0 = OFF (default)
1 = ON

P11

Time switch type for
Auto Timer

0 = individual days
(default)
1= all 7 days
2= 5-2 days

P12

Periodic pump run

0 = OFF (default)
1 = ON

P14

X1 external input

0 = no input (default)
1 = external sensor
2 = digital input

P15

Temperature
limitation

0 = OFF (default)
1 = ON

P16

Max. limitation
temperature for
floor heating

35…60 °C, step 1 °C
or
95…140 °F, step 1 °F
Default: 55 °C

P17

Window contact
features

0 = normally open
contact (default)
1 = normally closed
contact

P19

Sequential number
of room unit

0 = no display of
zone (RF off)
1 = zone number 1
(for standard RF)
(default)
6 = zone number 6

P20

RF learn

0 = OFF (default)
1 = ON

P21

Scanning rate for
the capacitive
buttons
Note: Shorter
scanning rate
means shorter
battery life

0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s

P22

Reload factory
settings

0 = OFF (default)
1 = reload

P23

Software version
information

No adjustment
possible

Содержание RDE100.1RFS

Страница 1: ...s Celsius Economy mode Button lock activated Escape Room temperature setpoint etc External input enabled Display of zone default 1 Permanent setpoint setting Heating On Weekday and time of day setting Weekday 1 Monday Weekday 7 Sunday Holiday mode setting Timer bar Current room temperature 2 Change operating mode 3 Set 4 Ok 5 Decrease value 6 Increase value 7 Battery holder RCR100RF 8 Indication o...

Страница 2: ...f comfort Select Auto Timer mode for the heating period and set the time switch according to your normal habits at home Select Economy or Holiday mode for longer periods of non occupancy and the summer period Do you want to set your Holiday mode Set Ok Mode Use the Holiday mode to set the thermostat to a constant room temperature while absent Press Set and select Press Ok to confirm Press or to ad...

Страница 3: ...me out and the transmitter exits the parameter setting mode Successful wireless learning 7 The green LED on the RCR100RF flashes for 10 minutes to indicate that the receiver has successfully completed wireless learning Recommendation 8 Additional test to ensure the wireless signal is fine On the RDE100 1 RF change the operating mode by pressing Mode or change the setpoint by pressing or On the RCR...

Страница 4: ...multaneously for 5 seconds Release the buttons and parameter P01 is displayed on the bottom segment Press or to scroll to the parameter that needs to be changed Press Ok to select the parameter Press or to change the value Press Ok to confirm the changed value Press Mode to exit the parameters without saving or wait for the program to exit automatically Parameter list Parameter no Description Sett...

Отзывы: