![Siemens RDE100.1RF Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/siemens/rde100-1rf/rde100-1rf_operating-instructions_384346004.webp)
4/4
Operating Instructions
CB1B1432en_01 / 2013-07-05
Siemens Building Technologies
Do you want to lock the buttons?
Mode
Press and hold
Mode
for at least 7 seconds to
activate a button lock. Repeat to unlock.
The unit operates normally when the buttons
are locked, but changes cannot be made.
Do you want to pair transmitter and
receiver?
+
–
Learn
Mode
Please refer to the instructions that come with
the receiver.
Do you want to change the parameters?
+
–
Ok
Mode
If you want to change control parameters,
proceed as follows:
•
Press
+
and
–
simultaneously for 5
seconds
•
Release the buttons and parameter
P01 is displayed on the bottom
segment
•
Press
+
or
–
to scroll to the parameter
that needs to be changed
•
Press
Ok
to select the parameter
•
Press
+
or
–
to change
the value
•
Press
Ok
to confirm the changed value
•
Press
Mode
to exit the parameters
without saving or wait for the program
to exit automatically
Parameter list
Parameter
no.
Description
Setting range
(default)
P01
Time format
1 = 24:00 hours
(default)
2 = 12:00 am/pm
P02
Selection of °C or
°F
1 = °C (default)
2 = °F
P03
Standard
temperature display
1 = room
temperature
(default)
2 = setpoint
P04
Temperature
sensor calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P06
Comfort setpoint
lock
0 = OFF (default)
1 = ON
locked
according to setting
in permanent
temperature setpoint
P08
Economy setpoint
lock
0 = OFF (default)
1 = ON
locked
according to setting
in permanent
temperature setpoint
P09
Buzzer
0 = OFF
1 = ON (default)
P10
Show frost
protection icon
0 = OFF (default)
1 = ON
P11
Time switch type
for Auto Timer
0 = individual days
(default)
1= all 7 days
2= 5-2 days
P12
Periodic pump run
0 = OFF (default)
1 = ON
P14
X1 external input
0 = no input (default)
1 = external sensor
2 = digital input
P15
Temperature
limitation
0 = OFF (default)
1 = ON
P16
Max. limitation
temperature for
floor heating
35…60 °C, step 1 °C
or
95…140 °F, step 1 °F
Default: 55 °C
P17
Window contact
features
0 = normally open
contact (default)
1 = normally closed
contact
P19
Sequential number
of room unit
0 = no display of
zone (RF off)
1 = zone number 1
(for standard RF)
(default)
…
6 = zone number 6
P20
RF learn
0 = OFF (default)
1 = ON
P21
Scanning rate for
the capacitive
buttons
Note: Shorter
scanning rate
means shorter
battery life
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22
Reload factory
settings
0 = OFF (default)
1 = reload
P23
Software version
information
No adjustment
possible