Siemens RDE-MZ6 Скачать руководство пользователя страница 3

3/3 

Operating Instructions 

CB1B1428en_02 / 2018-03-21 

Siemens Building Technologies 

Alternative: Driving the circulating pump/ 
boiler 

DIP 
switch 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

 

For this application: 

Step 1: Operate the DIP switch 

Power off the RDE-MZ6. 

Open the cover of the controller and set the DIP 
switch to position to 1 (ON). This means that 
zone 6 is now reconfigured for the circulating 
pump/boiler (default is OFF) 

 

 

Switch no. 

Application 
All valves (zone 1 to 6) 

OFF  OFF 

Pump/boiler (zone 6 only) 

ON  OFF 

 

Step 2: Making connections 

Connect zone 1 to zone 5 with valves or 
actuators.  

Connect zone 6 to the circulating pump or 
boiler. 

Step 3: Learning 

Power on the RDE-MZ6. 

Press and hold the 

RESET

 button for more 

than 10 seconds to make a complete reset. 

To pair zones 1 to 5, follow either option 1 or 2 
in the previous section. 

Zone 6: No pairing is required and the button is 
disabled.  

Functionality 

The output of zone 6 is enabled if 

either

 one or 

more of the remaining zones is turned on. Zone 
6 will turn off if 

all

 remaining zones are turned 

off (same as LED indication). 

Note:

 

Always power off the receiver before operating 
the DIP switch. 

Whenever a DIP switch has changed its 
position, it is highly recommended to make a 
complete reset and perform wireless learning 
again. 

Controller’s LED indication 

State of controller 

State of LED 

Power up (or reset) 

All 6 red and green LEDs flash 
alternately for 5 seconds and then 
extinguish. 
Note: If the receiver zone was 
previously programmed, it will 
immediately change to constantly 
red. 

Learning mode 

 

Successful learning 
mode  

The respective zone’s red and green 
LEDs flash alternately. 

The respective green LED will flash 
for 10 minutes if controller learning is 
successful. 

Signal ok and output 
status change 

 

 

For boiler or pump 
configuration 

The respective zone’s green LED is 
constantly lit. If the output status 
changes, the green LED will flash for 
3 seconds and then changes back to 
constantly green. 

Zone 6:  
Green LED is lit when relay is 
energized.  
Green LED is extinguished when 
relay is deenergized. 

Fail to receive 
wireless data 

If the respective zone of the 
controller fails to receive wireless 
data, the red LED will start to flash 
after 125 minutes. 

If RDE-MZ6 signal is recovered, it 
will return to the previous LED state. 

Respective zone has 
no ID 

The respective LED is extinguished. 

 

 