Installation:

•  Open the door by unscrewing the door knob.

•  Mount the controller on a vertical wall / plate free from 

vibrations with proper nuts and bolts. Refer Fig. 6 for 
mounting dimensions.

•  Remove the rubber grommets for the incoming and 

outgoing cable connections. (Refer Fig. 2).

•  Connect incoming and outgoing cables as follows  

(Refer Fig. 2):

  –  Use proper cable glands to ensure dust proofing. For 

conduit entry use packed washers.

  –  Select correct size of cables from Table 1.

  –  Remove approx. length of insulation as per following 

table:

Length of insulation 

removal (mm)

Cu cable size 

(mm

2

)

6

2.5

5

1.5

  –  Connect line and motor cables exactly as per wiring 

diagram pasted inside the cover of the starter.

  –  Terminate the incoming supply cables on terminal 

block TB1 & outgoing cables to motor on terminal 
block TB2 (Tightening torque - Refer table 2).

 

NOTE:

 LMRA is set in Manual mode (Factory setting)

•  Set the overload relay scale (Fig. 2) using proper screw 

driver as follows:

  –  Set the overload relay to rated current mentioned on 

motor name plate.

  –  Press green button of the contact block CB1 (Fig. 2) 

to start the motor and wait till it reaches to normal 
speed. Reduce the overload relay settings till it trips.

  –  Set the overload relay at slightly higher value.

  –  Allow a reset time appr. 4min. and reset the overload 

relay manually.

  –  Restart the motor. If the relay does not trip, consider 

the overload relay as properly set.

    If it trips, set it at little higher value and recheck.

  –  Press the red knob (Fig. 2) on the overload relay to 

stop the motor.

  –  Close the door by screwing the door knob.

Caution:

• 

During commissioning or maintenance always ensure 
that the main supply is disconnected by switching off 
the main switch & Rocker switch.

•  If the relay trips even when set at rated motor current 

the suitability of the controller / relay for the particular 
application should be checked with the nearest Siemens 
office.

Operation:

•  Ensure the door is locked.

•  Rotate the Mechanical Latch away from OFF push button. 

•  Switch On the rocker switch marked ‘I’.

•  Check the status of amber LED. Wait till amber LED is 

continuously ON then only proceed.

•  Depending upon Selector switch knob position for phase 

selection, Indication of incoming power supply voltage 
can be seen on Dual VA meter.

•  For starting the motor, press Green push button marked 

‘I’ (Fig. 1).

•  Line current of R phase is indicated by Dual VA meter.

•  Motor is ON when green LED is ON.

•  For stopping the motor press Red push button marked ‘O’ 

(Fig. 1).

•  For LMRA Auto / Bypass modes refer troubleshooting 

guide A5E50797230A.

•  Reset Operation

  –  If the overload relay trips, Reset manually. (Allow a 

reset time of approx. 4 min.)

Maintenance:

•  Switch off the Controller and Put Latch on the OFF push 

button, (marked ‘O’). 

Disconnect the main supply by 

switching the main switch & Rocker Switch Off before 
doing any maintenance.

•  Keep the interior dust free.

•  Re-tighten the terminal screws from time to time as per 

specified torque in table 2.

•  No maintenance is needed for overload relay. Please do 

not open the relay.

•  Replace contacts of the contactor if they were severely 

pitted or when only 40% of the original contact tips 
remains.

•  Replacement of Overload Relay (Refer Fig. 3):

  1.  Select a proper relay exactly as per the original.

  2.  Slightly loosen the outgoing terminal screws of the 

relay.

  3.  Disconnect the wires connected to the relay terminals.

  4.  Slightly loosen the outgoing terminal screws of the 

line contactor.

  5.  Follow instructions given in Fig. 3 for removal of 

relay.

  6.  Ensure that new relay hook is engaged in the slot on 

contactor.

  7.  Connect the relay terminals (L1, L2, L3) to (T1, T2, T3) 

of Q1 contactor. 

   

Care should be taken to fix the relay terminals & 
relay to contactor in the exact position shown in 

Fig. 2.

  8.  Tighten the contactor terminal (T1, T2, T3) screws.

  9.  Connect the relay terminals to Terminal block TB2.

  10. Re-connect all the disconnected wires and check 

connections by referring to the wiring diagram. 
(Fig.4)

For more Technical details like LMR-A wiring, operating 
sequence, mounting details etc., refer Installation & 
Troubleshooting guide no. A5E50797230A.

2

Содержание RAJA+ 3TE7121-1HC14-1A Series

Страница 1: ...ning Automatic Motor Restart LMRA has Auto mode selection Use this function with caution Motor will restart automatically when healthy power is restored back Reliable functioning of the equipment is only ensured with certified components Commissioning and maintenance by qualified personnel only NOTICE This product has been designed for environment A Use of this product in environment B may cause u...

Страница 2: ...e the Mechanical Latch away from OFF push button Switch On the rocker switch marked I Check the status of amber LED Wait till amber LED is continuously ON then only proceed Depending upon Selector switch knob position for phase selection Indication of incoming power supply voltage can be seen on Dual VA meter For starting the motor press Green push button marked I Fig 1 Line current of R phase is ...

Страница 3: ... TB4 LMR terminal connector Table 1 Motor Submersible Pump Rating At 415V Starter MLFB Contactor MLFB Thermal Overload relay MLFB Range A Max Full Load Current Amp for Motor Submersible Pump Recommended Max Back up HRC Fuse rating Siemens Make type 3NA7 500V Cu cable size mm2 3 2 2 3TE7121 1HC14 1A 3TS3010 0A 08K 3US5000 1H8K 5 8 6 5 20 1 5 5 3 7 3TE7121 1KC16 1A 3TS3110 0A 08K 3UW5102 1K 8 12 5 1...

Страница 4: ...0 0AZ8 08K 3 Contactor 3TS3110 0AZ6 08K 4 Contactor 3TS3110 0AZ8 08K 5 Contactor 3TS3210 0AZ6 08K 6 Contactor 3TS3210 0AZ8 08K 7 Contactor 3TS3210 0AZ6 08K 8 Contactor 3TS3210 0AZ8 08K 9 Contactor 3TS3311 0AZ6 08K 10 Contactor 3TS3311 0AZ8 08K 11 Thermal Overload Relay 3US5000 1H8K 12 Thermal Overload Relay 3UW5102 1K 13 Thermal Overload Relay 3UW5102 2A 14 Thermal Overload Relay 3UW5102 2B 15 The...

Страница 5: ...materials METALS Segregate into Ferrous types for recycling through authorized dealer PLASTICS Segregate as per material type for recycling through authorized dealer Because of the long lifetime of Siemens Products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is available at any time to answer disposal ...

Отзывы: