Siemens RAB10 Series Скачать руководство пользователя страница 5

RAB10 Series Two-pipe Fan Coil Room Thermostat 

Technical Instructions 

 

Document Number 155-524P25 

 

March 2, 2007 

Siemens Industry, Inc. 

Page 5

 

Drywall Mounting 

1.  Loosen the two screws at the bottom of thermostat. 

2.  Lift the bottom of the thermostat cover from the thermostat base and push up to 

remove cover. 

3.  Remove sub-base from back of thermostat. 

4.  Using the sub-base (packed with thermostat) as a template, mark the hole locations 

with a pencil. 

5.  Drill two 1/4-inch diameter holes for plastic wall anchors (provided). 

6.  Using a mallet, tap in the plastic wall anchors flush with wall. 

7.  Pull the wiring through the opening in the upper portion of the sub-base. 

8.  Level mounting plate. 

9.  Using the two wood screws provided, fasten sub-base to wall. Thermostat is not 

position sensitive. 

10.  Pull the wiring through the sub-base. 

11.  Position thermostat housing over the two mounting lugs located at the top of the 

sub-base, and press down on cover until bottom lugs snap in place. 

12.  Terminate wires per wiring instructions on the inside of thermostat cover. 

Optional:

  To set limit stops, remove gray tabs located on the setpoint knob and 

position high and low stops around perimeter of knob as required. 

 

Figure 2.  Setpoint Limit Stops. 

 

13.  Place all thermostat switches in the “down” position to allow cover switch sliders to 

fit over the switches. 

14.  Insert the top of the thermostat cover into the slots located on the top of the 

thermostat and press down. 

15.  Tighten the two screws at the bottom of the thermostat. 

16.  Return selector switches to the normal position. Adjust setpoint dial to desired 

setting. 

The installation is now complete. 

Содержание RAB10 Series

Страница 1: ...h Two mounting styles electrical wall box or drywall Wall plate adapter ARG70 included with electrical wall box mount styles Application Typically used in commercial high rise and light industrial buildings in conjunction with Zone valves Thermal valves Fans Product Numbers See Table 1 Technical Design The RAB10 fan coil room thermostat is based on a two wire gas diaphragm technology Operation Hea...

Страница 2: ...nction is selected RAB10 1 the heating and cooling contacts are always open and the fan works at the selected speed Changeover The control algorithm can be selected with a switch located on the front of the controller change over switch Adjustments The required temperature can be selected by a rotating setpoint adjuster at the front of the thermostat High and low setpoint limit stops can be engage...

Страница 3: ...113 1 42 8 mm Color Ivory white with gray selector knobs Ambient Conditions Operation Temperature 32 F to 122 F 0 C to 50 C Relative humidity 95 Transport Storage Temperature 4 F to 122 F 20 C to 50 C Relative humidity 95 Wiring Screw terminals for wires of 2 16 AWG or 1 14 AWG Minimum 20 AWG Housing Material Plastic Enclosure rating NEMA1 Bellows Environmentally friendly gas Agency Certification ...

Страница 4: ...unit must be de energized and the operating voltage checked before opening An ARG70 wall plate adapter provided with electrical wall box mount models must be used to mount to a 2 4 inch or 4 4 inch electrical wall box An ARG70 wall plate adapter must be used to meet UL and cUL requirements The thermostat must be mounted on a flat wall All local electrical regulations must be complied with If there...

Страница 5: ...vided fasten sub base to wall Thermostat is not position sensitive 10 Pull the wiring through the sub base 11 Position thermostat housing over the two mounting lugs located at the top of the sub base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions on the inside of thermostat cover Optional To set limit stops remove gray tabs located on the setpoin...

Страница 6: ...stat cover from the thermostat base and push up to remove cover 3 Using the four screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting S...

Страница 7: ...e thermostat cover from the thermostat base and push up to remove cover 3 Using the two screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mou...

Страница 8: ...fore servicing Metal part is not grounded Diagrams L Operating voltage M1 3 speed fan N Neutral N1 Room thermostat G1 Control output fan speed I Low G2 Control output fan speed II Medium G3 Control output fan speed III High ZV Zone valve or thermal valve W Y Control output actuator Figure 5 Wiring T Room temperature SD Switching differential SP Room temperature setpoint W Valve output signal heati...

Страница 9: ...r company names mentioned herein may be the trademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 524P25 Printed in the USA Pag...

Отзывы: