PAGE 2

RAA02... INSTALLATION

s

Fix the sub-base using two of the available

holes marked ’F’.

Step 1.

Remove the cover by releasing clip ‘C’ with a

screwdriver.

Step 2.

The unit can now be fixed to either the sub-

base or the wall by means of two screws

maximum diameter 3.5mm using the holes

marked ‘B ’ provided in the base.

Step 3.

NB: The thermostat is for use with fixed wiring

only.

You can limit the temperature range or lock the

set limit by means of tappets as shown.

Step 4.

ELECTRICAL CONNECTIONS

Thread the cables through the slot in the base,

make the connections to the terminals as

shown on the diagram inside the cover and

illustrated on the right.

TECHNICAL DATA

Contacts rating:

16 (6) A/250V

Temperature range:

5 - 30°C

Differential:

0.8°C

Protection class:

I

Degree of protection:

IP30

Number of automatic cycles: II (100,000)

Temperature rate of change:

1K/15min.

Switch action:

2B

Dirt resistance:

normal ambient

Note: Remote switch with class <A>

disconnection, i.e. 3mm. contact gap in each

pole must be provided. Nominal cross sectional

area: min. 1.5mm

2

Max. 2.5mm

2

.

NOTES

U

2

3

1

Load

Pump

Valve

etc.

No neutral required

Must be earthed

N

L

+-