Siemens RAA Series Скачать руководство пользователя страница 2

Technical Instructions 

RAA Series Room Thermostats 

Document Number 155-519P25 
March 2, 2007 

Page 2

  

Siemens Industry, Inc. 

 

 

Table 1.  Product Numbers. 

Mounting Style 

Product 
Number 

Control 

Switch 

Scale 

Electrical Wall 

Box (with wall 

box adapter) 

RAA10CW 

Heating only or cooling only 

None 

Celsius (concealed) 

RAA20UW 

Heating only or cooling only 

None 

Fahrenheit and Celsius 

Drywall

1

 

RAA10C 

Heating only or cooling only 

None 

Celsius (concealed) 

 

RAA20U 

Heating only or cooling only 

None 

Fahrenheit and Celsius 

 

Operation 

The room thermostat is based on a two-wire, gas membrane technology. 

When the room temperature falls below the selected setpoint, the thermostat closes the 
heating contact. If the room temperature is over the selected setpoint, the cooling 
contact is closed. 

Adjustments 

A rotating setpoint adjuster inside the thermostat can select the required temperature. 

 

RAA10… No adjustments can be made outside the thermostat. The cover must be 
removed to adjust setpoint. 

 

RAA20… High and low setpoint limit stops can be engaged to limit temperature 
range. 

Warning/Caution Notations 

 

WARNING: 

 

Personal injury, or loss of life may occur if 
you do not perform a procedure as specified. 

CAUTION: 

 

Equipment damage, or loss of data may 
occur if you do not follow a procedure as 
specified. 

 

Specifications 

Operating voltage 

24 to 120 Vac, 277 Vac 

Frequency 

50/60 Hz 

Setpoint adjustment range 

50°F to 85°F (10°C to 30°C) 

Setpoint limit stops are adjustable (except RAA10…) 

Switching differential (SD) 

<1.8°F (1°C), fixed 

Switch rating 

6A RES, 3.5A FLA, 12A LRA 

Switch action 

Single-Pole, Double-Throw (SPDT) 

Output   

Two-position (On/Off) 

Weight 

5 oz. (0.14 kg) 

Dimensions 

 

  RAA10… 

3.80 × 3.92 × 1.42 inches 

   

(96.4 × 99.6 × 36 mm) 

  RAA20… 

3.80 × 3.92 × 1.68 inches 

   

(96.4 × 99.6 × 42.8 mm) 

Color 

Ivory white 

Содержание RAA Series

Страница 1: ...ing voltage Two mounting styles electrical wall box or drywall Wall plate adapter ARG70 included with electrical wall box mount styles Dual setpoint temperature scale RAA20 or tamperproof concealed setpoint RAA10 Product Numbers See Table 1 Accessory ARG70 Wall box adapter Application Typically used in Schools Public buildings Storage rooms Maintenance rooms Temporary heat for building constructio...

Страница 2: ...stments A rotating setpoint adjuster inside the thermostat can select the required temperature RAA10 No adjustments can be made outside the thermostat The cover must be removed to adjust setpoint RAA20 High and low setpoint limit stops can be engaged to limit temperature range Warning Caution Notations WARNING Personal injury or loss of life may occur if you do not perform a procedure as specified...

Страница 3: ...g Material Plastic Enclosure rating NEMA1 Bellows Environmentally friendly gas Wiring Screw terminals for wires of 2 16 AWG or 1 14 AWG minimum 20 AWG Agency Certification Conforms to CE requirements UL listed to 873 E35918 cUL listed to Canadian standard C22 2 No 24 93 Table 2 Control Valves Part Number Description Technical Instructions SFA71U 24V NC 155 321P25 SFA11U 120V NC SFA208U 25 208V NC ...

Страница 4: ...t must be de energized and the operating voltage checked before opening An ARG70 wall plate adapter provided with electrical wall box mount models must be used to mount to a 2 4 inch or 4 4 inch electrical wall box An ARG70 wall plate adapter must be used to meet UL and cUL requirements The thermostat must be mounted on a flat wall All local electrical regulations must be complied with If there ar...

Страница 5: ...ortion of the sub base 8 Level the mounting plate 9 Using the two wood screws provided fasten sub base to wall Thermostat is not position sensitive 10 Pull the wiring through the thermostat housing 11 Position thermostat housing over the two mounting lugs located at the top of the sub base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions on the ins...

Страница 6: ...2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with one No 4 24 5 8 inch long screw provided with the thermostat at the bottom only 7 Pull wires through the sub base 5 8 Clip thermostat base 6 at the top of the sub base and snap the bottom in...

Страница 7: ...r ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with one No 4 24 5 8 inch long screw provided with the thermostat at the bottom only 7 Pull wires through the sub base 5 8 Clip thermostat base 6 at the top of the sub base and snap the bo...

Страница 8: ...ded Wiring Diagrams Heating Mode Cooling Mode D1 Heating device D2 Cooling device L Operating voltage N Neutral N1 Room thermostat T Thermal switch W Heating control output Y Cooling control output Figure 5 RAA10 and RAA20 Wiring Operating Diagrams Heating Mode Cooling Mode T Room temperature SD Switching differential SP Room temperature setpoint W Heating output signal Y Cooling output signal Fig...

Страница 9: ... mentioned herein may be the trademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them toSBT_technical editor us sbt siemens com Document No 155 519P25 Printed in the USA Page 9 Dimensions C...