Installation Instructions 
October 5, 2009 

Page 2 of 3 

Siemens Industry, Inc.

 

Instructions 

1.  Drill a 7/8-inch diameter hole into the duct at the 

desired location of the sensor. 

2.  Decide if the sensor will be mounted directly to 

the duct or if the mounting flange will be used.  

 

Sensor Mounting Bracket Installation 

a.  Use the bracket as a template, and drill 

two holes with a No. 26 (0.147-inch) drill 
bit. See Figure 1(B).  

b.  Attach the sensor mounting bracket and 

gasket to the duct using two No. 8 × 1-
inch sheet metal screws. See 
Figure 1(C1). 

c.  Insert the sensor in the duct through the 

bracket and tighten the mounting screw 
to set the insertion depth. See 
Figure 1(C2). 

 

Direct installation: 

a.  Remove the sensor cover. 

b.  Use the base as a template, and drill four 

holes with a No. 26 (0.147-inch) drill bit. 
See Figure 1(B). 

c.  Insert the probe through the gasket and 

into the hole. Secure the head to the duct 
with four No. 8 × 1-inch sheet metal 
screws. 

3.  Attach conduit or plenum wire to the sensor 

base. See Figures 1 and 2. 

4.  If you are using conduit, pull the field wiring 

through the conduit and into the sensor base. 

5.  Connect the field wiring to the sensor terminal 

block on the base. See Figures 3 through 7 for 
wiring diagrams. 

6.  Reinstall the sensor cover. See Figure 1(C6). 

The installation is now complete. 

 

    

 

   

 

Figure 1.  RH/T Duct Sensor Installation. 

Figure 2. Conduit or Plenum 

 

 

 Cable Wiring Installation. 

NOTE: 

Figure 2 shows how to connect the conduit or plenum cable to the sensor head. 

.