Technical Instructions 

Q-Series Outdoor Air and Critical Environment  

Document Number 155-755 

Relative Humidity and Relative Humidity & Temperature Sensors 

February 28, 2013 

Page 6 

 

Siemens Industry, Inc. 

 

Specifications 

Power Supply 

Operating voltage 

24 Vac + 20% or 13.5 to 35 Vdc 

Frequency 

50/60 Hz at 24 Vac 

Power consumption 

< 1 VA 

Humidity element 

Operating range 

0 to 100% rh 

Measurement range 

0 to 95% rh 

Accuracy at room temperature (73°F [20°C]) 

+ 2% rh, 0 to 95% rh 

Time constant 

Approx. 20 s in moving air 

Output signal, linear (terminal U1) 

0 to 10 Vdc = 0 to 100% rh 

 

 

 

Max. + 1 mA 

Operating temperature 

- 40°F to 158°F (- 40°C to 70°C) 

Temperature effect 

< 0.1% per degree Celsius 

Sensing element 

Capacitive humidity sensing element 

Output signal (rh only units) 

4 to 20 mA or 0 to 10 Vdc, 0 to 100% 

   

linear, 

proportional 

Output signal (rh/T units) 

4 to 20 mA or 0 to 10 Vdc, 0 to 100% 

   

linear, 

proportional 

Polarity protection 

Yes 

Temperature element 
(for combination rh/T 
units only) 

Operating temperature, jumper selectable 

32°F to 122°F (0°C to 50°C) or 

 

 

 

-31°F to 95°F (-35°C to 35°C), 

 

 

 

- 40°F to 158°F (- 40°C to 70°C) 

Time constant @ 32°F to 122°F 

Approximately 20 s in moving air 

(0°C to 50°C) and 10 to 80% rh 

Accuracy 
 

@ 32°F to 122°F (0°C to 50°C) 

+ 1.8°F (+ 1°C) 

 

@ -31°F to 95°F (-35°C to 35°C) 

+ 1.4°F (+ 0.8°C) 

 

@ 32°F to 158°F (0°C to 70°C) 

+ 1.8°F (+ 1°C) 

Output signal 

4 to 20 mA or 0 to 10 Vdc, 0 to 100% 

   

linear, 

proportional 

Calibration adjustments 

None 

General 

Installation 

18 AWG cable length shared in 

 

 

 

conduit with other sensor wiring. 

 

 

 

750 ft (229 m) maximum 

Connections Screw 

terminals 

Dimensions 
 

Outdoor air probe 

6" OD × 3.3" L (15 mm × 84 mm) 

 

Outdoor air housing 

3.1" L × 2.3" W × 1.5" D 

 

 

 

(80 mm × 60 mm × 40 mm) 

 

Shield (mounted) 

3.43" H × 3.5" W × 4.1" D  

 

 

 

(87 mm × 89 mm × 104 mm) 

Voltage requirement 

13.5 to 35 Vdc 

Material type 

Polycarbonate plastic 

Protection class rating 

IP 65 (NEMA 4) 

Agency certification 

  

Conforms to 

EMC Directive 89/336/EEC

 

UL Listing 

UL873 XAPX 

cUL Listing 

Canadian Standard C22.2 No. 24-93 

 

Conforms to Australian EMC 

Radio Communication Act 1992 

Framework Radio Interference Emission 

AS/NZS 3548 

Standard 

 

Содержание Q Series

Страница 1: ...ure Very high measuring accuracy across the entire measuring range Capacitive humidity measurement Precise stable humidity sensing Available in 2 and 2 certified models Optional display Recalibration service available QFA41 Series only Application The Q Series Outdoor Air rh and rh T Sensors are for use in HVAC applications where high accuracy and short response times for measuring relative humidi...

Страница 2: ... 24 Vac or 13 5 to 35 Vdc QFA4171 None QFA4171D 2 certified Yes Field selectable 32 F to 122 F 0 C to 50 C 31 F to 95 F 35 C to 35 C or 40 F to 158 F 40 C to 70 C Active 4 to 20 mA 0 to 100 Active 4 to 20 mA 13 5 to 35 Vdc Accessories 74 662 01040 US rigid 1 2 inch conduit adapter AQF3101 Sensor filter cap replacement AQF3150 Replaceable 2 sensor tip AQF4150 Replaceable certified sensor tip AQF310...

Страница 3: ... active 0 to 10 Vdc or 4 to 20 mA output signal corresponding to a temperature range of 32 F to 122 F 31 F to 95 F or 40 F to 158 F 0 C to 50 C 35 C to 35 C or 40 C to 70 C The measuring range is selected by repositioning factory supplied jumpers Resistive Load Diagram Figure 1 Output Signal Terminal I1 I2 Mechanical Design The room sensor consists of housing printed circuit board connection termi...

Страница 4: ...age at signal output U2 I2 is 0V 4 mA after 60 seconds The humidity signal at signal output U1 I1 increases to 10V 20 mA If the humidity sensor is faulty the voltage at signal output U1 I1 is 10V 20 mA after 60 seconds The temperature signal remains active Calibration Certificates QFA41 Series only The sensor and its exchangeable AQF4150 measuring tip are numbered registered and calibrated prior t...

Страница 5: ... the north or northwest side of the building If possible mount in the middle of the wall at least 8 feet 2 5 meters above the ground Do not mount above or below windows above doors or ventilation shafts or below balconies or eaves Mounting Position The sensor and AQF3100 must be mounted in a vertical position with the sun shield at the top NOTE When using the AQF3100 outdoor mounting kit the senso...

Страница 6: ...ment for combination rh T units only Operating temperature jumper selectable 32 F to 122 F 0 C to 50 C or 31 F to 95 F 35 C to 35 C 40 F to 158 F 40 C to 70 C Time constant 32 F to 122 F Approximately 20 s in moving air 0 C to 50 C and 10 to 80 rh Accuracy 32 F to 122 F 0 C to 50 C 1 8 F 1 C 31 F to 95 F 35 C to 35 C 1 4 F 0 8 C 32 F to 158 F 0 C to 70 C 1 8 F 1 C Output signal 4 to 20 mA or 0 to ...

Страница 7: ...mens Industry Inc Page 7 Wiring Terminals QFA3100 QFA3101 QFA3160 QFA3160D QFA4160 QFA4160D QFA3171 QFA3171D QFA4171 QFA4171D Figure 3 Wiring Terminals QFA4160 QFA4160D Front View Connector fitted body removed QFA4171 QFA4171D Front View Connector fitted body removed Figure 4 Connectors Dimensions Figure 5 QFA31 Series Sensors with AQF3100 Dimensions in Inches Millimeters ...

Страница 8: ...Product or company names mentioned herein may be the trademarks of their respective owners 2013 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 USA 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions Continued Figure 6 QF...

Отзывы:

Похожие инструкции для Q Series