7 / 12
Siemens
PXC3.E... Room automation stations
CM1N9203en_05
Building Technologies
2015-11-23
Technical data
Operating voltage
(24V~,
⊥
)
Safety extra-low voltage SELV or
protection by extra-low voltage PELV
Half-wave load
AC 24 V -15 % / +20%
48...63 Hz
Symmetric
Operating data
Processor
PXC3.E...-100A (V6)
PXC3.E7... (V5.1)
Texas Instruments AM3352, 600 MHz
Atmel AT91SAM9G20, 400 MHz
Memory
PXC3.E...-100A (V6)
PXC3.E7... (V5.1)
512 MB SDRAM (DDR3)
512 MB NAND Flash
128 MB SDRAM (SDR)
256 MB NAND Flash
Power consumption
Max. permissible input current
AC 24 V (through terminals 5 and 6)
Total max. 10 A
(Ext. fusing compulsory: max. T 10 A
melting fuse or max. C 10 A circuit
breaker)
Base load (without loading by modules
and field devices)
8 VA / 0.33 A
Island bus supply *)
30 VA / 1.25 A
KNX PL-Link supply *) **)
12 VA / 0.50 A
DALI supply *)
9 VA / 0.37 A
*) The bus supplies can be switched off via tool if not used.
**) The NX PL-Link supply MUST be switched off via tool if an external
bus supply is used.
Transit power AC 24 V
TX-IO (island bus)
KNX PL-Link: AC 24V
(terminals 3, 4)
AC 24 V / 6 A
(terminals 7 and 8, for additional
AC 24 V consumers)
144 VA / 6 A
48 VA / 2 A
144 VA / 6 A
(only if the sum of 10 A at terminals
5 and 6 is not exceeded)
Fusing of the supply
outputs for field supply
AC 24 V /2 A (KNX PL-Link, terminals
3 and 4)
PTC resistor, short-circuit proof
Caution!
AC 24 V (terminals 7 and 8)
No internal fusing
Island bus conductor V~
T 10A fuse (slow, exchangeable)
Response to power /
communication failure
•
Energy reserve (supercap) to support real-time clock (3 days).
•
Start-up time after power failure: approx. 90 s
Ethernet interface
Plug
2 x RJ45, screened
Interface type
100BaseTX, IEEE 802.3 compatible
Bit rate
10 / 100 Mbps, autosensing
Protocol
BACnet over UDP/IP
USB interface
Plug
Type B (USB device)
Data rate (USB 1.1)
12MBit/s
Galvanic isolation of
⊥
No
Protective circuit against surges and
over current
Yes (balancing currents are limited, also
in the GND conductor)