Testing the Tripping Transformers
Table 5. Static Trip II and First Generation Tripping
Transformers
Tripping
Exciting
Maximum
Transformer Rating
Voltage RMS
Exciting Current
RMS
80:1
33.5
0.25
150:1
67
0.15
200:1
67
0.15
250:1
67
0.15
400:1
67
0.05
600:1
134
0.05
800:1
134
0.03
1000:1 and up
134
0.02
Table 6. Limitrip Sensor Transformers “O” to “Y” (Siqnal)
Terminals
Sensor
Exciting
Maximum
Transformer Ratio
Voltage RMS
Exciting Current
RMS
80:1
4.6
0.25
200:1
7.0
0.15
400:1
17.0
0.05
600:1
32.0
0.05
800:1
34.0
0.03
1000:1 and up
34.0
0.02
Table 7. Static Trip II R L. Style Tripping Transformer
Tripping
Exciting
Maximum
Transformer Rating
Voltage RMS
Exciting Current
RMS
80:1
30
0.25
150:1
40
0.15
200:1
45
0.15
250:1
50
0.15
400:1
70
0.05
600:1
100
0.05
800:1
100
0.03
1000:1 and up
134
0.02
Table 8. Static Trip III Tripping Transformer
Tripping
Exciting
Maximum
Transformer Rating
Voltage RMS
Exciting Current
RMS
150:5
33.5
0.25
200:5
50
0.15
300:5
67
0.10
400:5
67
0.10
600:5
67
0.05
800:5
134
0.03