Technical data
6.1 Input
SITOP PSU300M/300B
40
Manual, 11.2014, C98130-A7574-A2-2-7629
6EP1424-3BA00
(12 V / 20 A)
6EP1436-3BA20
(24 V / 17 A)
6EP1437-3BA20
(24 V / 30 A)
Input
3-phase, AC
3-phase, AC
3-phase, AC
Rated voltage value Ue rated
400-500 V
400-500 V
400-500 V
Voltage range
320 ... 575 V
320 ... 575 V
320 ... 575 V
Wide-range input
Yes
Yes
Yes
Overvoltage strength
2.3 × Ue rated, 1.3 ms
2.3 × Ue rated, 1.3 ms
2.3 × Ue rated, 1.3 ms
Power failure buffering
at Ia rated, min
•
Remark: at Ue = 400 V
20 ms
20 ms
20 ms
Rated line frequency
50-60 Hz
50-60 Hz
50-60 Hz
Line frequency range
47 ... 63 Hz
47 ... 63 Hz
47 ... 63 Hz
Input current / at rated value of
input voltage 400 V
0.7 A
1.2 A
1.6 A
Input current / at rated value of
input voltage 500 V
0.6 A
1 A
1.3 A
Inrush current limiting
(+25° C), max.
18 A
18 A
56 A
I²t, max
0.8 A
2
s
0.8 A
2
s
2.24 A
2
s
Integrated input fuse
None
None
None
Protection in the line feeder
cable (IEC 898)
Required: 3-pole, coupled miniature circuit breaker 6 ...
10 A characteristic C or circuit breaker 3RV2011-1DA10
(setting 3 A) or 3RV2711-1DD10 (UL 489)
Required: 3-pole, coupled
miniature circuit breaker
10 ... 16 A characteristic C
or circuit breaker
3RV2011-1DA10 (setting
3 A) or 3RV2711-
1DD10 (UL 489)
Figure 6-1
Power failure buffering
Содержание PSU300B
Страница 8: ...Safety notes SITOP PSU300M 300B 8 Manual 11 2014 C98130 A7574 A2 2 7629 ...
Страница 38: ...Installation 5 2 Output side connection SITOP PSU300M 300B 38 Manual 11 2014 C98130 A7574 A2 2 7629 ...
Страница 58: ...Technical data 6 9 Dimension drawing SITOP PSU300M 300B 58 Manual 11 2014 C98130 A7574 A2 2 7629 ...
Страница 78: ...Environment SITOP PSU300M 300B 78 Manual 11 2014 C98130 A7574 A2 2 7629 ...