background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033060-19

4

Terminals 10, 11 and 12 provide external CAN network connection. All
others are not used.

TB2

Relay outputs; 1 for Alarm, 1 for Trouble and 2 User-programmable relays
that are set to NOT USED by default. These outputs are rated 2A @ 30VDC/
120VAC (.6 PF).

Under normal system operation, the alarm and trouble relays are
controlled by the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3 (Cerberus PRO Modular). However, if the
HNET fails (and the initiating card cannot communicate with the PMI/
PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO Modular), the DLC will control the ALARM
and TROUBLE relays. The User programmable relays are activated by the
PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO Modular) output logic as programmed by
the Zeus tool. When the system is operating normally, these relays are
controlled by the output logic only. (See Figure 4.)

TB3

24VDC Power Limited Output Terminal. This terminal output is limited to
4A. When it is exceeded, it will shut down, light its associated diagnos-
tics LED and send a fault condition to the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular)

.

This output is normally connected to the modules and cards located on
the door of the enclosure or to remote CAN network modules. This
output is power limited to NFPA 70 per 760. All wiring must be in
accordance with Article 760 of NEC or local building codes. (See Figure 2.)

Output Voltage: 24VDC +10%, -15%
Output Current: 4A max
TB3-1: (+) terminal
TB3-2: (-) terminal

TB4

24VDC Non-Power Limited Output Terminal. This terminal is non-power
limited and can supply up to 12A. When the current draw is exceeded, it
shuts down, lights its associated LED and sends a fault condition to the
PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular),
FCM2041-U3 (Cerberus PRO Modular).

This output is normally connected to the input terminals of the CC-5.
This output must remain within the enclosure or within 20 feet in rigid
conduit. All wiring must be in accordance with Article 760 of NEC or
local building codes. (See Figure 2.)

Output Voltage: 24VDC +10%, -15%
Output Current: 12A max
TB4-1: (+) terminal
TB4-2: (-) terminal

The total cumulative sum of the 24VDC output (power l non-power limited)

must not exceed 12A. Over current draw will initiate a PSC-12 shut down.

 The main AC power line must be turned OFF prior to installation.

19

24

18

13

TB2

NO

NO

NO

NO

NC

NC

NC

NC

C

C

C

C

PROGRAMMABLE

COMMON

TROUBLE

RELAY

OUTPUT

ALARM

RELAY

OUTPUT

USER

RELAY 2

OUTPUT

USER

RELAY 1

OUTPUT

Figure 4

TB2 Wiring Diagram

Figure 3

TB1 Wiring Diagram

S = SHIELD TIE POINT.

CONNECT AT ONE

PSC-12 ONLY.

1

6

12

7

TB1

+

+

S

S

+

– S

+

– S

FMT

RISER

LVM

MONITOR

SPEAKER

LVM

MICROPHONE

CAN

Содержание PSC-12

Страница 1: ...on the battery input It provides connection to a tamper switch and terminal tie points for system signals The PSC 12 communi cates directly to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to report fault conditions and allows the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the status of the powe...

Страница 2: ...igo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the state of the power supply and its current load and can send a diagnostics command to the PSC 12 It also provides the control of the relays The degrade ALARM bus and degradeTROUBLE bus will override the command that is sent by the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to the Alar...

Страница 3: ... its outputs 24V 12A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC non power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC output due to current overload or short circuit 24V 4A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC power output...

Страница 4: ...mally connected to the modules and cards located on the door of the enclosure or to remote CAN network modules This output is power limited to NFPA 70 per 760 All wiring must be in accordance with Article 760 of NEC or local building codes See Figure 2 Output Voltage 24VDC 10 15 Output Current 4A max TB3 1 terminal TB3 2 terminal TB4 24VDC Non Power Limited OutputTerminal This terminal is non powe...

Страница 5: ...wers the CC 5 CC 2 modules It also contains all the communication signals and system signal bus that is necessary for the proper operation of the system These connectors are power limited If the PSC 12 is located in a different row in the enclosure an optional extended ribbon cable Model BCL P N 599 633997 must be used Output Voltages 24VDC 6 2VDC Max Current 2A 24VDC 2A 6 2VDC PRE INSTALLATION Th...

Страница 6: ...ocated either inside or outside of the enclo sure to perform this installation procedure If the Mounting Plate is located inside the enclosure you will have to gain access to it by opening the enclosure Inner and Outer doors If the Mounting Plate is located outside of the enclosure place it in front of you so that the word TOP is at the top and away from you The PSC 12 can occupy any position in t...

Страница 7: ...ors at the top of the PSC 12 are power limited The terminals and connectors at the bottom of the PSC 12 are non power limited Refer to Figure 7 Use a separate or dedicated circuit breaker and run the earth ground from a suitable source to the PSC 12 Check local requirements Conduit is not an acceptable Earth Ground Conductor Figure 6 Mounting The PSC 12 On The Optional CAB MP TOP SLIDE DOWN UNTIL ...

Страница 8: ... 3 batteries are required connect them to the system with the Battery Cable Conversion Kit P N 545 634222 following the steps listed below 1 Using the 12 in long wire assembly connect the two batteries together as shown in Figure 7 Secure each end of the assembly to the battery with a 10 32 x 3 4 screw and lock nut 2 Attach the quick disconnects to the positive and negative battery terminals with ...

Страница 9: ...r Power Supply Load and Battery Calculations The PSC 12 power supply load and battery size calculations are performed by the Zeus tool based on the equipment in the physical view Once all of the equipment is inserted into the physical view for each enclosure and a successful compile is performed the results of the calculations are shown in the report view From theTools menu select Report Generatio...

Страница 10: ...P N 500 633917 with the BTX 2 and BTX 3 models Battery System Electrical Rating Input Voltage 24VDC 10 15 Input Current 15A max Minimum Battery size 15AH Maximum Battery size 100AH Battery Max Charge Current 5A full charge mode ELECTRICAL RATINGS e g a t l o V t u p n I z H 0 6 0 5 C A V 0 2 1 z H 0 6 0 5 C A V 0 2 2 z H 0 6 0 5 C A V 0 4 2 t n e r r u C t u p n I C A V 0 2 1 x a M A 5 3 C A V 0 2...

Страница 11: ... needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional ...

Страница 12: ...Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033060 19 Siemens Gebäudesicherheit GmbH Co oHG D 80930 München Document ID A6V10239105 ...

Отзывы: