Siemens PS-5N7 Скачать руководство пользователя страница 2

2

Figure 2

PS-5N7 Wiring Diagram in the RCC-1/-1F Enclosure (Without a PIM-1)

Figure 3

PS-5N7 Wiring Diagram in MME-3 or MSE-2 (With a PIM-1)

Four male/female standoffs are provided in
each backbox in the correct location for
installing the PS-5N7. Place the PS-5N7
over the existing female standoffs. Fasten it,
using the threaded portion of the standoffs
as screws. Use the cable provided (See
Figures 1 and 2) to connect P1 on the
PS-5N7 to P1 on the ANN-1.

Note: If a PIM-1 is used in the config-

uration, refer to the instructions
below.

Using the PS-5N7 with a PIM-1

To support a remote printer, use a PIM-1
with the PS-5N7.

Note:  The PIM-1 and PS-5N7 have the

same mounting holes.

When  using a PIM-1 with  the PS-5N7 in
an MME-3 or MSE-2 backbox (See Figure 3):

1. Mount the PIM-1 first, as shown.

2. Use the four male/female standoffs

provided with the PS-5N7 as screws.

3. Attach the PIM-1 to the female

standoffs.

4. Connect the cable from P1 of the

ANN-1 board to P1 on the PIM-1.

5. Next, mount the PS-5N7 on the same

standoffs, using the four screws from
the PIM-1 kit.

6. Attach the cable supplied with the

PIM to P2 on the PIM-1.

7. Plug the cable from P2 of the PIM-1

into P1 of the PS-5N7; see Figure 3.

Содержание PS-5N7

Страница 1: ...See the Note at the top of page 2 if using a PIM 1 Figure 1 PS 5N7 Wiring Diagram in MME 3 or MSE 2 Without a PIM 1 1 MME 3 Install in the upper right hand corner See Figure 1 2 MSE 2 Install in the upper right hand corner See Figure 1 3 RCC 1 1F Install in the lower right hand corner See Figure 2 Note In a special application which is described on page 7 the PS 5N7 can be used as a source of powe...

Страница 2: ...ration refer to the instructions below Using the PS 5N7 with a PIM 1 To support a remote printer use a PIM 1 with the PS 5N7 Note The PIM 1 and PS 5N7 have the same mounting holes When using a PIM 1 with the PS 5N7 in an MME 3 or MSE 2 backbox See Figure 3 1 Mount the PIM 1 first as shown 2 Use the four male female standoffs provided with the PS 5N7 as screws 3 Attach the PIM 1 to the female stand...

Страница 3: ...e terminals 3 and 4 in this configuration See Figure 5 for additional wiring information Refer to the PSR 1 Instal lation Instructions P N 315 090911 for more details on Style 4 networks Using PS 5N7 with Style 7 4 Wire Network Connections Do not place the PS 5N7 module in the last position on a Style 7 Network Use a NET 7 at each end of the network to provide proper supervision Use screw terminal...

Страница 4: ...0mA max ELECTRICAL CONNECTIONS Refer to the following Installation Instructions as needed MMB 2 P N 315 095097 MMB 3 P N 315 048860 PSR 1 P N 315 090911 PS 35 P N 315 085062 PLM 35 P N 315 093495 PAD 3 P N 315 099082 MXL MXLV Manual P N 315 092036 6 DO NOT place the PS 5N7 at the end of the network Style 7 only 7 This configuration is power limited to NFPA 70 according to NEC 760 8 Refer to Wiring...

Страница 5: ...nce that results in a 4 volt drop due to Imax To calculate the total line loss use the fol lowing equation Rmax Vmax Imax Where Vmax 4V in all cases The Rmax result obtained with this equation is the total of all wire resistance in ohms in the 24 VDC supply lines The following power supplies are compat ible with the PS 5N7 They are listed with their maximum output current Imax MMB 1 amp PSR 1 2 am...

Страница 6: ...1 P N 315 090267 Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information Using the PS 5N7 to Drive an OMM 1 In order to add Voice hardware to a remote enclosure use a PS 5N7 module to drive an OMM 1 if the following conditions apply 1 The remote enclosure is not connected to the MMB and 2 There are multiple MXLs that are n...

Страница 7: ...osure ACM 1 P N 315 092083 TBM 2 P N 315 093782 VSM 1 VLM 1 VFM 1 P N 315 092064 For additional information on this configuration refer to the following Installation Instructions Refer to Wiring Specification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information ...

Страница 8: ...P N 315 092729 13 Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN ...

Отзывы: