Communication setup

The SmartLinx PROFIBUS DP-V1 module is a slave on the bus, and does not use any 
Siemens device parameters for configuration. Set the rotary switches on the module to 
the desired slave address. Other settings are provided in the GSD file or are automatically 
detected.

GSD files

A PROFIBUS master requires the GSD file for each device on the network. The GSD file 
contains parameter and capability information regarding the slave device. 

For the PROFIBUS DP-V1 module, the GSD file is HMS_b1813.gsd (included on the 
accompanying DVD).

Baud rate

The SmartLinx PROFIBUS DP-V1 module automatically configures itself to the correct 
baud rate for the PROFIBUS DP-V1 network. Follow the PROFIBUS guidelines with 
regards to bus length and baud rate.

Bus address

Set the two rotary switches to the address for this slave.

Use a slave address switch in the range 03 to 99. 
This example shows the value “06.”

Содержание PROFIBUS DP-V1

Страница 1: ...Operating Instructions SmartLinx PROFIBUS DP V1 08 2015 Edition Communication ...

Страница 2: ...ll Rights Reserved Disclaimer of Liability This document is available in bound version and in electronic version We encourage users to purchase authorized bound manuals or to view electronic versions as designed and authored by Siemens Siemens will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions While we have verified the contents of thi...

Страница 3: ... setup 9 GSD files 9 Baud rate 9 Bus address 9 Configuring the slave device 10 Module identification 11 3 2 10 4 Smartlinx Module Type Read only 11 3 2 10 5 Smartlinx Protocol Read only 11 Application layer 12 Data access methods 12 Data map 12 Slot index Acyclic 14 Data types 20 Integer 20 Bit values 20 Floating point number 20 Unsigned 32 bit Integer UINT32 20 Split values 21 Text messages 21 Re...

Страница 4: ...ii mmmmm Table of Contents ...

Страница 5: ...s smpi siemens com For the complete library of Siemens operating instructions go to www siemens com processautomation WARNING Relates to a caution symbol on the product and means that failure to observe the necessary precautions can result in death serious injury and or considerable material damage WARNING Means that failure to observe the necessary precautions can result in death serious injury a...

Страница 6: ...appropriate continent then select the country followed by the city Click on Next For on line technical support go to www siemens com automation support request Enter the device name or order number then click on Search and select the appropriate product type Click on Next You will be prompted to enter a keyword describing your issue Then either browse the relevant documentation or click on Next to...

Страница 7: ...d the HydroRanger 200 HMI can use this module PROFIBUS is an open standard controlled by PROFIBUS industry groups worldwide More information is available on the website www profibus com Note This product is intended for use in industrial areas Operation of this equipment in a residential area may cause interference to several frequency based communications 1 SmartLinx is a registered trademark of ...

Страница 8: ...on Compatible with the MultiRanger 200 HMI and the HydroRanger 200 HMI Communication settings Baud rate 9 6 Kbaud to 12 Mbaud automatically detected Termination Switch selectable open or special active termination as per PROFIBUS specification see Termination switch on page 6 Cable Belden PROFIBUS cable 3079A or equivalent ...

Страница 9: ...s compatible with the Siemens devices MultiRanger 200 HMI and the HydroRanger 200 HMI Product Software revision MultiRanger 200 HMI 2 00 HydroRanger 200 HMI 2 00 Notes Install the SmartLinx module so that the mounting holes align and the pin connectors mate correctly Correct cable routing is important for electromagnetic noise suppression Follow the routing instructions contained your device opera...

Страница 10: ... the PROFIBUS DP V1 specifications for details Note RTS is used in some equipment to determine the direction of transmission In normal applications only A line B line and shield are used Termination Setting Switch position Open not used OFF 390 220 390 ON 1 The termination switch is not present on all modules bus cable shield bus ground GND A line bus 5V Vcc B line RTS GND 5V Line A Line B ...

Страница 11: ...t being executed or no power Fieldbus Online Green Bus online data exchange possible Green flashing Clear mode Red Application stopped OFF Bus not online or no power Fieldbus Offline Red Bus offline OFF Bus not offline or no power Fieldbus Diagnostics OFF No diagnostics present or no power Red flashing Error in Configuration Data Red flashing Error in Parameter Data Red flashing Error in initializ...

Страница 12: ...ring the slave device on page 10 for lengths supported by the SmartLinx module and see your PLC documentation for setting the I O length variable 2Hz Error in user parameter data Indicates that the length and or contents of the user parameter data set during initialization of the module is greater than the length and or contents set during configuration of the network See Configuring the slave dev...

Страница 13: ...ter requires the GSD file for each device on the network The GSD file contains parameter and capability information regarding the slave device For the PROFIBUS DP V1 module the GSD file is HMS_b1813 gsd included on the accompanying DVD Baud rate The SmartLinx PROFIBUS DP V1 module automatically configures itself to the correct baud rate for the PROFIBUS DP V1 network Follow the PROFIBUS guidelines...

Страница 14: ...ation 1 Open hardware configuration from the main project window 2 Install the PROFIBUS DP V1 GSD file HMSB1813 gsd 3 Assuming you have a PLC and rack setup with a PROFIBUS DP network go to the hardware catalog and select the PROFIBUS DP V1 card under PROFIBUS DP Additional field devices General Anybus s DPV1 IM 4 Drag the Anybus s DPV1 IM device to the PROFIBUS DP network 5 In the popup screen se...

Страница 15: ...ation Please refer to the Parameters chapter of your Siemens device operating instructions for more details about the subject 3 2 10 4 Smartlinx Module Type Read only Identifies the module used 3 2 10 5 Smartlinx Protocol Read only Identifies the protocol used the value varies according to the module and whether it is a Type 1 or Type 2 Value Module 0 No module present 1 Anybus DT module 2 Anybus ...

Страница 16: ...on describes the read write process data available from the MultiRanger 200 HMI or the HydroRanger 200 HMI Please refer to the Parameters chapter of the your Siemens device operating instructions for details about the parameters used in the table below Word offset Description Data type Bytes Parameter 0 PV Point 1 Process variable for Point 1 in Programmed units PV is displayed as an IEEE float in...

Страница 17: ... 2 n a 11 Digital inputs The value of the digital inputs are mapped into this Word Bit 0 is the Digital Input 1 Word 2 2 9 2 3 Discrete Input 1 Scaled State 12 Relay outputs The value of the relay outputs are mapped into this Word Bit 0 is the Relay Output 1 Word 2 13 mA input 1 The value of the analog input is mapped into this Word Float 4 2 6 6 Raw mA Input Value 15 Totalizer 1 References the To...

Страница 18: ...52 1 Fuzz Filter 2 11 5 6 UINT8 2 Echo Lock 2 11 5 4 UINT8 3 Echo lock up UINT8 4 Echo lock down UINT8 5 Echo Lock Window 2 11 5 5 UINT16 6 1 or 2 53 1 Algorithm 2 11 2 2 UINT8 2 Blanking 2 2 6 Float32 3 Range Extension 2 2 7 Float32 4 Submergence Detection 2 11 2 8 UINT8 5 Shot pulse Mode 2 1 17 UINT8 6 Echo Time Filtered 3 2 9 7 Float 32 7 Echo Time Raw 3 2 9 8 Float32 8 Spike Filter 2 11 2 7 UI...

Страница 19: ...e Filter 2 3 5 UINT8 6 Rate Filter Time 2 3 6 Float32 7 Rate Filter Distance 2 3 7 Float32 25 1 or 2 59 Shot Delay 2 1 16 UINT32 4 1 or 2 60 Scan Time 2 1 15 Float32 4 1 or 2 61 1 Primary Measuring Device 2 13 2 UINT8 2 Flow Exponent 2 13 4 1 Float32 3 Maximum Head 2 13 4 2 Float32 4 Maximum Flow 2 13 4 3 Float32 5 Zero Head 2 13 4 5 Float32 6 Flow Time Units 2 13 4 4 UINT8 7 Flowrate Decimal 2 13...

Страница 20: ... 6 9 Float32 8 1 or 2 70 Sensor Offset 2 2 5 Float32 4 1 or 2 71 Auto Sound Velocity 2 11 1 8 Float32 4 1 or 2 72 Auto Zero Head 2 13 3 Float32 4 1 or 2 73 1 Noise Average 3 2 9 5 UINT8 2 Noise Peak 3 2 9 6 UINT8 3 Noise minimum UINT8 3 1 or 2 74 1 Rate 3 2 6 6 Float32 2 Pump Records 3 2 7 Float32 8 1 or 2 75 Auto False Echo Suppression 2 11 3 2 UINT8 1 1 or 2 77 1 LOE Timer 2 4 2 Float32 2 Fail s...

Страница 21: ... 3 97 1 Vessel Shape 2 7 2 UINT8 2 Maximum Volume 2 7 3 Float32 3 Dimension A 2 7 4 Float32 4 Dimension L 2 7 5 Float32 13 3 98 1 Sensor Mode 2 1 3 UINT8 2 Material 2 1 6 UINT8 3 Rate Filter 2 3 5 UINT8 4 Transducer 2 1 5 UINT8 5 Empty 2 2 4 Float32 6 Span 2 2 2 Float32 12 4 50 Relay Duration 2 10 1 3 INT32 4 4 51 Preset Applications 2 8 1 3 UINT8 1 4 52 1 Run ON Interval 2 8 2 7 1 INT32 2 Delay B...

Страница 22: ...te INT32 2 Comm Addr1 INT32 3 Comm Addr2 INT32 4 Comm Size1 INT32 5 Comm Terminate INT32 6 Comm Bits UINT8 7 Comm Error UINT16 8 Comm Error Count INT32 9 Comm Fieldbus Interface INT16 10 Comm Fieldbus Type INT16 31 5 60 Diagnostic information for testing 240 5 61 1 Shot Synchro 2 1 13 UINT8 2 Scan Delay 2 1 14 UINT32 5 5 62 Units 2 1 1 UINT8 1 5 63 1 Default Auxiliary Reading 2 12 7 INT16 2 Auxili...

Страница 23: ...roll Access UINT8 4 Local Display Backlight 2 12 1 UINT8 5 Main Display UINT8 9 5 82 84 1 Decimal Position 2 12 4 UINT8 2 Convert Reading 2 12 5 Float32 3 Offset Reading 2 12 6 Float32 9 5 88 1 Tag 3 1 1 UINT8 2 Message 3 1 3 UINT8 3 Descriptor 3 1 2 UINT8 4 Date Last Configured 3 1 10 UINT8 4 Slot Absolute index Parameter name number Data type Total bytes ...

Страница 24: ... be expressed in terms of percent example Span or has no meaningful value the special number 22 222 is returned Try requesting the parameter in units or refer to the Siemens device operating instructions to understand the format and use of the requested parameter Bit values Bits are packed into registers in groups of 16 bits 1 word In this operating instructions bits are numbered from 00 to 15 wit...

Страница 25: ...a parameter is determined by the following formula For storing to the device value xx 128 x 256 yy 128 For reading from the device xx value 256 128 yy value 256 128 where is the modulus operator The modulus can be computed by following these steps value1 value 256 value2 remainder of value1 value3 value2 x 256 yy value3 128 It may simplify parameter to notice xx most significant byte of value 128 ...

Страница 26: ...197302 mmmmm Application layer 30004 ERR 30005 ERR1 30006 OPEN 30007 SHORT 30008 PASS 30009 FAIL 30010 HOLD 30011 LO 30012 HI 30013 DE 30014 EN 30015 Parameter has not been set 32768 Value is less than 20 000 32767 Value is greater than 20 000 Number Text message ...

Страница 27: ... relay not used 0 OFF Undesignated Level Alarm 1 Level LoLo Level Alarm 2 Level LL Lo Level Alarm 3 Level L Hi Level Alarm 4 Level H HiHi Level Alarm 5 Level HH In bounds Alarm 6 In bounds Out of bounds Alarm 9 Out of bounds Rate of Level Change Alarm 12 Rate of Change Temperature Alarm 15 Temperature Loss of Echo LOE Alarm 20 LOE Transducer Cable Fault Alarm 16 Cable Fault Flow Totalizer 22 Total...

Страница 28: ...e sure that it is the correct one see GSD files on page 9 Check the wiring to the module In particular check that you have lines A and B connected correctly Verify that you have set the correct address on the module Also please note that the module does not see a charge until the power has been cycled Verify that the Read and Write block sizes are correct Other devices dropping out If the network ...

Страница 29: ...us Diagnostics 7 Offline 7 Online 7 Floating point number See Data types G GSD files 10 H Hardware 5 I Installation 5 Integer See Data types L LED 7 M Module identification 11 N Network Address 9 O Operation 7 LED 7 R Relay function codes 23 S Safety 1 Setup communication 9 SmartLinx PROFIBUS DP V1 3 application compatibility 4 Cable 4 Communication settings 4 intended areas for use 3 interface 3 ...

Страница 30: ......

Страница 31: ......

Страница 32: ...chpubs smpi siemens com Subject to change without prior notice For more information www siemens com processautomation www siemens com level www siemens com weighing Siemens Canada Limited 1954 Technology Drive P O Box 4225 Siemens AG 2015 A5E356197302 Rev AA ...

Отзывы: