background image

Technical Instructions  
Document No. 155-199P25 
October 24, 2005 
 

Page 6

  

Siemens Industry, Inc. 

Sizing, Continued 

 

The maximum capacity the valve must deliver. 

 

The maximum line pressure differential the valve actuator must close against. 

See 

Application Bulletin (AB)-1 Control Valve Selection and Sizing 

(155-285) for further 

recommendations. 

See Tables 3 and 4 for valve capacities. 

Mounting and 
Installation 

Install the valve so that the flow follows the direction of the arrow indicated on the valve 
body.  

For best performance, install the valve assembly with the actuator above the valve body. 
The valve and actuator can be installed in any position between vertical and horizontal. 
It is not recommended to install the valve assembly so that the actuator is below 
horizontal or up side down. 

Allow sufficient space for servicing the valve and actuator. See Table 6 for valve body 
dimensions. See Figure 5 and Table 7 for dimensions of the service envelope 
recommended around the actuator.  

NOTE: 

Instructions for field mounting an actuator, wiring diagrams, and start-up 
are covered in the Technical Instructions and Installation Instructions for 
each actuator. 

Service 

Replace the valve if inoperable. 

Dimensions 

See Table 6 for valve body dimensions. The letters in Figure 5 refer to the valve 
centerline to top of actuator, the actuator width, and service envelope dimensions in 
Table 7. 

 

  

Figure 4.  Three-way Valve. 

 

Table 6.  Three-way Valve Dimensions. 

Valve Size 

inch (mm) 

Weight 

lb (kg) 

1/2 

(15) 

2-3/4 

(70) 

2-15/16 

(74) 

1-5/16 

(33) 

1.10 

(0.5) 

3/4 

(20) 

3-1/4 

(83) 

3-9/16 

(90) 

1-5/16 

(33) 

1.44 

(.65) 

(25) 

3-7/8 

(98) 

3-15/16 

(99) 

1-9/16 

(39) 

2.20 

(1.0) 

Содержание Powermite 599 Series

Страница 1: ...0 01 of Cv Application A typical application for the Powermite three way valve is the mixing of hot or chilled water for convectors fan coil units unit conditioners radiation reheat coils and similar terminal units requiring an actuator that delivers a minimum of 45 pounds force 200 N Product Numbers Table 1 Product Numbers Flow Rate Line Size Product Cv Kvs inch mm Number 0 4 0 34 1 2 15 599 0113...

Страница 2: ...travel Stroke 7 32 inch 5 5 mm Material Body UNS CA844 bronze or forged brass C37700 Body trim Brass Stem Stainless steel ASTM A582 Type 303 Packing Ethylene propylene O ring Operating Controlled medium Water glycol solutions to 50 Medium temperature range 35 F to 250 F 2 C to 120 C Maximum inlet pressure See Table 2 Maximum recommended differential pressure for modulating service 25 psi 173 kPa R...

Страница 3: ...0 8 8 10 1 11 3 12 4 13 9 2 5 3 5 4 3 5 0 5 6 6 1 7 1 7 9 9 7 11 2 12 5 13 7 15 8 17 7 19 4 22 4 5 7 7 8 0 8 9 10 11 3 12 6 15 5 17 9 20 0 21 9 25 28 31 35 3 4 6 3 8 9 10 9 12 6 14 1 15 4 17 8 20 24 28 32 35 40 45 49 55 1 10 14 1 17 3 20 22 24 28 32 39 45 50 55 63 71 77 87 Table 4 Maximum Water Capacity Cubic Meters per Hour m3 hr Valve Size in mm Pressure Differential kPa 1 10 20 30 40 50 60 80 K...

Страница 4: ...esired pressure drop 5 psi Choose a 1 inch 25 mm valve Cv 10 Table 5 Close off Pressures Action Valve Size Inches mm SSB Actuator psi kPa NC Upper port 1 2 0 4 Cv 1 6 15 mm 0 34 Kvs 1 37 70 483 1 2 2 5 Cv 4 15 mm 2 15 Kvs 3 44 40 276 3 4 and 1 20 mm and 25 mm 30 207 NO Bottom port 1 2 0 4 Cv 1 6 15 mm 0 34 Kvs 1 37 25 172 1 2 2 5 Cv 4 15 mm 2 15 Kvs 3 44 15 103 3 4 and 1 20 mm and 25 mm 10 69 ...

Страница 5: ... hold the last commanded position See the Technical Instructions of the various actuators for additional information Figure 3 Sizing The sizing of a valve is important for correct system operation An undersized valve will not have sufficient capacity at maximum load An oversized valve can initiate cycling and the seat and throttling plug can be damaged because of the restricted opening Correct siz...

Страница 6: ...tall the valve assembly so that the actuator is below horizontal or up side down Allow sufficient space for servicing the valve and actuator See Table 6 for valve body dimensions See Figure 5 and Table 7 for dimensions of the service envelope recommended around the actuator NOTE Instructions for field mounting an actuator wiring diagrams and start up are covered in the Technical Instructions and I...

Страница 7: ...the Actuator and Recommended Service Envelope Dimensions in Inches Millimeters Actuator Actuator Prefix Code Valve line Size Center line to Top of Actuator H1 Service Height H Actual width of the Actuator W1 Service Width W SSB 254 255 1 2 15 4 7 8 124 13 1 8 330 3 1 4 83 11 1 4 282 3 4 20 4 7 8 124 13 1 8 330 3 1 4 83 11 1 4 282 1 25 5 1 8 130 13 3 8 335 3 1 4 83 11 1 4 282 ...

Страница 8: ... Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 155 199P25 Printed in the USA Page 8 Parts Of The Valve Table 8 Three way Bronze Forged Brass Valves Item Part Name Part No Q ty Material 1 Bonnet Ass y 1 2 Spri...

Отзывы: