Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
AC Power
ports
2 kVDC
Signal ports
5 kV (Fail-Safe
Relay Output)
DC Power
ports
5 kV
HV Impulse
AC Power
ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
IEEE Test
IEEE 1613
Clause
Description
Test Levels
Enclosure Contact
±8 kV
C37.90.3
9
ESD
Enclosure Air
±15 kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
Signal ports
±4 kV @ 2.5 kHz
DC Power ports
±4 kV
AC Power ports
±4 kV
Fast
Transient
Earth ground ports
±4 kV
Signal ports
2.5 kV common
mode @ 1MHz
DC Power ports
2.5 kV common and
differential mode @ 1MHz
C37.90.1
7
Oscillatory
AC Power ports
2.5 kV common and
differential mode @ 1MHz
Signal ports
5 kV (Failsafe Relay)
DC Power ports
5 kV
HV Impulse
AC Power ports
5 kV
Signal ports
2 kVAC (Failsafe Relay)
DC Power ports
1.5 kVDC
C37.90
6
Dielectric
Strength
AC Power ports
2 kVAC
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40
°F), 16 Hours
RUGGEDCOM RS8000
Installation Manual, 12/2021, C79000-G8976-1020-06
29