5
Keyboard & Mouse
(Using Splitter Cable)
See NCC-2F Installation Instructions, P/N 315-049430
(Default COM Post Assignment Shown)
See Note 2
See Notes 2 and 3
Flexible Conduit
(User Supplied)
Conduit
AC Main
120 VAC 60Hz
AC Main
120 VAC 60Hz
Computer (rear view)
Junction
Box
(user
supplied)
Parallel Printer (rear view)
120 VAC/60 Hz
LPT
2
LAN 2
VGA
VIDEO
TOUCH
DC12V
MONIT
OR
CARD
CPU
CARD
USB
POR
TS
PARALLEL
POR
T
SERIAL
POR
TS
SOUND
CARD
NCC-2F
COM
3
NCC-2F
COM
5*
LAN 1
(For
NCC
Key)
LCD Monitor
(rear view)
LPT
1
1
2
3
4
5
6
7
8
Junction
Box and Cover
(user supplied)
Bushing
(user
supplied)
Approved Flexible
Conduit Connector
(user supplied)
Approved 1/2” Flexible
Metallic/Nonmetallic
Conduit (user supplied)
Power
Connection
Box
(not
required for
Rack Mount
or Console
Installations)
.
Video
COM
2
COM
1
1
2
3
4
5
1
2
3
4
5
12V
5A
Power
Supply
Not Supervised
NOTES:
1.
Connect the PAL-1 printer to LPT1 port on the rear of the Siemens Building Management system computer.
2.
NFPA 72 Proprietary and Local System installation requires that the computer, monitor and printer be UL
rated for fire (Siemens models SCDXP/XPWAN-B, SCDXP/XPWAN-BT, SCD-19L-2, SCD-19TL-2, UHW-
W717-00T-M, UHW-W717-00L-M, UHW-W7AO-22T-C, UHW-W7AO-19T-C, UHW-W7XN-00T-M, UHW-
W7XN-00L-M, UHW-0000-22T-L, UHW-0000-42T-L, UHW-0000-22L-L, UHW-0000-42L-L and PAL-1
respectively).
3.
PAL-1 printer is supervised for paper out, AC loss, and printer parallel cable removal by the build
management software at the computer.
4.
All circuits, except AC Input, are power limited.
5.
All cables must be in rigid conduit and cannot leave the room.
Figure 6
Siemens Building Management System
Siemens Building Management System (NCCXP-G or -GL, NCCI7-G or -GL, Desigo CC, and
Cerberus DMS)
1.
The PAL-1 can be used as a supervised journaling or logging printer when connected to a UL listed
Siemens Building Management System computer to meet the requirements of an NFPA 72 proprietary
system. The printer is supervised for paper out, AC loss, and printer parallel cable removal.
2.
Refer to the FireFinder-NCC Operation, Installation and Maintenance Manual, P/N 315-049679, or Desigo
CC Engineering Guide, Document ID A6V10376170, or Cerberus PRO Engineering Guide, Document ID
A6V10376202, for more details on connecting and programming the PAL-1.
3.
Figure 6 shows the proper installation of PAL-1 with a NCCXP-G or -GL, NCCI7-G or -GL computer,
Desigo CC or Cerberus DMS.
Electrical Ratings
120 VAC, 60 HZ, 3A.