Air damper actuators GSD...1
CE2N4603en
Smart Infrastructure
2019-11-25
Commissioning notes
For commissioning, the following reference documentation must be available::
•
This data sheet.
•
HVAC job diagram.
Check to ensure that all permi
ssible values as contained in the section “Technical
data" have been observed.
•
Check for proper mounting and ensure that all mechanical settings correspond
to the plant-specific requirements. Additionally, ensure that the dampers are
tightly closed when in the closed position.
•
Check the direction of rotation.
•
Fasten the actuator securely to avoid twisting and blocking of the actuator.
•
Check to ensure that the cables are connected in accordance with the plant
wiring diagram
(see “Wiring diagrams”).
•
The operating voltage AC/DC 24 V (SELV/PELV) or AC 230 V must be within
the tolerance values.
Power supply AC/DC 24 V wires red (1), black (2)
Positioning signal AC/DC 0 V
•
Wire orange (7) ON:
•
Wire orange (7) OFF:
Actuator turns counter-clockwise
Actuator turns clockwise
Power supply AC 230 V wires brown (3), blue (4)
Positioning signal AC 230 V
•
Wire white (7) ON:
•
Wire white (7) OFF:
Actuator turns counter-clockwise
Actuator turns clockwise
Internal Diagrams
GSD12..1A
GSD32..1A
Reference
Environmental conditions
Mechanical check
Electrical check
Functional check
GSD121.1A
GSD126.1A
GSD321.1A
GSD326.1A