Technical Instructions
OpenAir GEB Non-Spring Return, 24 Vac,132 lb-in, Rotary Electronic Damper Actuators
Document Number 155-318P25
May 19, 2014
Page 12
Siemens Industry, Inc.
WARNINGS:
Installations requiring
Conformance:
•
Except for the auxiliary switches (See
Warning
above) all wiring for actuators must
be safety extra-low voltage (SELV) or protective extra-low voltage (PELV) per
HD384.
•
Use safety transformers per EN61558 with double isolation, designed for 100%
duty-cycle for supplying SELV or PELV circuits.
•
Over-current protection for supply lines is maximum 10A.
CAUTION:
Do not parallel GEB13x actuators with any other type of actuator.
Wire Designations
Each wire has the standard symbol printed on it. See Table 3.
Figure 17.
Modulating 0 to 10 Vdc Control.
24 Vac Power Supply.
Figure 18.
Floating Control.
24 Vac Power Supply.
Table 3.
Actuators
Symbol
Function
Terminal
Designations
Color
24 Vac
Power Supply
1
Supply (SP)
G
Red
2
Neutral (SN)
G0
Black
6
Control signal clockwise
Y1
Violet
7
Control signal counterclockwise
Y2
Orange
8
0 to 10 Vdc input signal
Y
Gray
9
Output for 0 to 10 Vdc position indication
U
Pink
Auxiliary
Switches
S1
Switch A Common
Q11
Gray/red
S2
Switch A N.C.
Q12
Gray/blue
S3
Switch A N.O.
Q14
Gray/pink
S4
Switch B Common
Q21
Black/red
S5
Switch B N.C.
Q22
Black/blue
S6
Switch B N.O.
Q24
Black/pink
Potentiometer
P1
Feedback Potentiometer 0 to 100% P1 - P2 a
White/red
P2
Feedback Potentiometer Common
b
White/blue
P3
Feedback Potentiometer 100 to 0% P3 - P2 c
White/pink