Accessories to functionally extend the actuators are available, e.g., rotary/linear sets
and weather protection cover; see data sheet N4697.

Technical data

Operating voltage / Frequency
Power consumption

GEB13..1: Running
GEB16..1: Running

Holding

AC 24 V

±

20 % / 50/60 Hz

4 VA / 3.5 W
6 VA / 5.5 W
1.5 W

Operating voltage / Frequency
Power consumption

GEB33..1

AC 230 V

±

10 % / 50/60 Hz

3 VA / 3 W

Nominal torque
Maximum torque (blocked)
Nominal rotary angle / Max. rotary angle
Runtime for 90° rotary angle

15 Nm
30 Nm
90° / max. 95°

±

150 s (50 Hz) / 125 s (60 Hz)

Input voltage Y (wires 8-2)
Max. permissible input voltage

DC 0...10 V / DC 2...10 V
DC 35 V

Input voltage Y (wires 8-2)

Non-adjustable characteristic function
Adjustable characteristic function

Offset Uo
Span

U

DC 0...35 V
DC 0...10 V / DC 2...10 V
DC 0...5 V
DC 2...30 V

Output voltage U (cores 9-2)

Max. output current

DC 0...10 V
DC

±

1 mA

Change of resistance (wires P1-P2)
Load

0...1000

< 1 W

Contact rating
Voltage (no mixed operation AC 24 V / AC 230 V)
Switching range for auxiliary switches
Setting increments

6 A resistive, 2 A inductive
AC 24...230 V
5°...90°

Cross-section
Standard length

0.75 mm

2

0.9 m

Degree of protection as per EN 60 529 (note mounting instructions) IP 54

Insulation class
AC 24 V, feedback potentiometer
AC 230 V, auxiliary switch

EN 60 730
lll
ll

Operation / Transport

Temperature
Humidity (non-condensing)

IEC 721-3-3 / IEC 721-3-2

32...+55 °C /

32...+70 °C

< 95% r. h. / < 95% r. h.

Product safety: Automatic electrical controls for household and
similar use
Electromagnetic compatibility (EMC):

Immunity for all models, except GEB132.1x; GEB332.1x
Immunity for GEB132.1x; GEB332.1x
Emissions for all models

Conformity:

Electromagnetic compatibility
Low voltage directive

Conformity:

Australian EMC Framework
Radio Interference Emission Standard

EN 60 730-2-14
(Type 1)

EN 61 000-6-2
EN 50 082-1
EN 50 081-1

89/336/EEC
73/23/EEC

Radio Communication Act 1992
AS / NZS 3548

Actuator W x H x D (see "Dimensions")
Damper shaft:

Round
Square
Min. shaft length

81 x 192 x 63 mm
6.4...20.5 mm
6.4...13 mm
20 mm

Without packaging: GEB1...1

GEB33..1

1 kg
1.1 kg

Disposal

The document on technical basics and the environmental declaration provide
information on environmental compatibility and disposal of this device.

Accessories, spare
parts

AC 24 V supply
(SELV/PELV)

AC 230 V supply

Function data

Positioning signal for GEB16..1

Characteristic functions
for GEB161.1, GEB166.1
for GEB163.1, GEB164.1

Position indicator
for GEB16...1

Feedback potentiometer
for GEB132.1 / GEB332.1

Auxiliary switches
for GEB..6.1 / GEB164.1

Connection cables

Degree of protection of housing

Protection class

Environmental conditions

Standards and directives

Dimensions

Weight

Содержание OpenAir GEB 1

Страница 1: ...ning signal position indicator feedback potentiometer self adaptation of the rotary angle range and adjustable auxiliary switches for supplementary functions This data sheet provides a brief overview of these actuators Please refer to the technical basics in CM2Z4621en for a detailed description as well as information on safety engineering notes mounting and commissioning Use For damper areas up t...

Страница 2: ... counter clockwise Position indication Mechanical Rotary angle position indication by using a position indicator Position indication Electrical The feedback potentiometer can be connected to external voltage to indicate the position Position indicator Output voltage U DC 0 10 V is generated proportional to the rotary angle U depends on the rotary direction of the DIL switch Auxiliary switch The sw...

Страница 3: ...e mounting instructions IP 54 Insulation class AC 24 V feedback potentiometer AC 230 V auxiliary switch EN 60 730 lll ll Operation Transport Temperature Humidity non condensing IEC 721 3 3 IEC 721 3 2 32 55 C 32 70 C 95 r h 95 r h Product safety Automatic electrical controls for household and similar use Electromagnetic compatibility EMC Immunity for all models except GEB132 1x GEB332 1x Immunity ...

Страница 4: ...2 7 orange OG Control signal AC 0 V counter clockwise Y 8 gray GY Pos signal DC 0 10 V 2 10 V 0 35 V U 9 pink PK Position indication DC 0 10 V Actuators AC 230V N 4 blue BU Neutral conductor Y1 6 black BK Control signal AC 230 V clockwise Y2 7 white WH Control signal AC 230 V counter clockwise Auxiliary switch Q11 S1 gray red GY RD Switch A Input Q12 S2 gray blue GY BU Switch A Normally closed con...

Отзывы: