The VAV compact controller is supplied with two prewired connecting and communication
cables.

G..B181.1E/KN

Χ

p

(G)

(CE+) (CE-)

1

1

2

(G0)

2

35

47

G

01

Tool

Tool = Configuration and maintenance interface
(Series E and later: 7-pin connector)

Power supply and communication cables

Core designation

Core color

Terminal code

Description

Cable 1: Power / black sheathing

1

red (RD)

G

System voltage AC 24 V

2

black (BK)

G0

System neutral AC 24 V

Cable 2: Communication / green sheathing

1

red (RD)

CE+

KNX CE+

2

black (BK)

CE-

KNX CE+

Note

The operating voltage at terminals G and G0 must comply with the requirements under
SELV or PELV.
Safety transformers with twofold insulation as per EN 61558 required; they must be designed
to be on 100 % of the time.

Dimensions

G..B181.1E/..

Measurements in mm

min. 100

m

in

.

20

0

min. 80

m

in

.6

8

20

ø

7

2

5

18

0

X

8 - 16 mm
12.8 mm
15 mm

3547M01

14

x

12

X =

4

.1

5

71

26

.5

87

158

137

Ø 3...8

43

4

1

.3

6

1

9.

6

Содержание OpenAir G B181.1E/KN Series

Страница 1: ...KNX communication GDB181 1E KN with 5 Nm nominal torque GLB181 1E KN with 10 Nm nominal torque Operating voltage AC 24 V Supports KNX S Mode LTE Mode and PL Link For plants with variable or constant air volume flow Actual values for volume flow damper position and differential pressure Operating modes for volume flow control or position control s ...

Страница 2: ...gineering Commissioning Tool A6V11159913 Software versions VAV Compact Controllers series G are designed for using ETS device profile v2 x however ETS device profile v1 x is supported for backward compatibility reasons Firmware software version Series E Series F Series G Production period 10 2011 03 2014 03 2014 01 2017 01 2017 Bus module FW version 4 16 4 18 4 24 ETS device profile v1 x supported...

Страница 3: ...essory mounting holes for fixation of the damper actuators Mounting positions IP54 protection in following mounting positions Accessory mounting holes 2 Cf mounting instr M3547 2 Not to be used for fixation of the actuator use anti rotation bracket instead Maintenance The damper actuators are maintenance free Disconnect the electrical connections from the terminals if you want to work at the devic...

Страница 4: ...t failed 3 3 Function or part of the function available in PL Link operation only Addressing and bus test with push button The VAV compact controllers can be set into addressing programming mode by push button ƒ Press push button 0 1s and 1s ƒ KNX bus wiring OK LED turns red until addressing programming is finished ƒ KNX bus wiring not OK LED stays dark Reset with push button The VAV compact contr...

Страница 5: ...r the PPS2 interface using ACS931 or AST20 Some of them can be adjusted during commissioning operation or maintenance and are accessible over a bus connection alternatively Parameter Range Description Factory settings Operating mode VAV POS VAV setpoint volume flow 0 100 POS setpoint damper position 0 100 VAV Opening direction CW R CCW L Opening direction of air damper CW R Adaptive positioning Of...

Страница 6: ...ives to defined position ƒ Keep last position Actuator keeps position without flow control Backup position Backup position 0 100 Position the damper drives to in case of communication interruption 50 Tab card advanced Hysteresis COV 4 volume flow 1 20 Threshold for the relative volume flow COV below this value are not sent over the bus 1 Min repetition time volume flow 10 900 s Minimum waiting tim...

Страница 7: ...tes m 3 s 0 2 32 1 8 Fault Transmit 1 1 0 1 0 1 005 _Alarm 1 bit 0 No alarm 1 Alarm 9 Overridden Transmit 1 1 0 1 0 1 002 _Bool 1 bit 0 False 1 True 10 Override position 1 Receive 1 1 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 11 Override position 2 Receive 1 1 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 12 Balancing mode Receive 1 1 1 0 0 1 003 _Enable 1 bit 0 Disable 1 Enable 13 Vmin Receive ...

Страница 8: ... default therefore no faults are transmitted from the actuator over the KNX bus 4 Setpoint Setpoint 0 100 for volume flow or position depending on the operating mode 5 Damper position Relative damper position 0 100 An opening range less than 0 90 can be normalized to 0 100 if adaptive positioning is set to on 6 Volume flow relative Volume flow relative to the settings of Vnom Vmin and Vmax 7 Volum...

Страница 9: ... Power supply Number of cores and cross sectional area 2 x 0 75 mm 2 Communication Number of cores and cross sectional area 2 x 0 75 mm 2 Service interface Terminal strip 7 pin grid 2 00 mm Communication Communication protocol Connection type KNX TP galvanically isolated Bus load 5 mA Degree of protection Degree of protection Degree of protection acc to EN 60529 see mounting instruction IP54 Safet...

Страница 10: ...ng 0 6 kg Dimensions 71 x 158 x 61 mm Suitable drive shafts Round shaft with centering element 8 16 mm 8 10 mm Square shaft 6 12 8 mm Min drive shaft length 30 mm Max shaft hardness 300 HV Air volume flow controller Type 3 position controller with hysteresis Vmax adjustable resolution 1 factory setting 100 20 120 Vmin adjustable resolution 1 factory setting 0 20 100 Vn f dpn adjustable resolution ...

Страница 11: ...code Description Cable 1 Power black sheathing 1 red RD G System voltage AC 24 V 2 black BK G0 System neutral AC 24 V Cable 2 Communication green sheathing 1 red RD CE KNX CE 2 black BK CE KNX CE Note The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV Safety transformers with twofold insulation as per EN 61558 required they must be designed to be on 10...

Страница 12: ...ternational Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel 41 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2017 Technical specifications and availability subject to change without notice Document ID CE1N3547en_c Edition 2018 10 10 ...

Отзывы: