background image

A6V10324661_en--_m

3

OOHC941 Selectable Fixed Temperature

Threshold Profiles

Fixed temperature 135 °F
Fixed temperature 145 °F
Fixed temperature 155 °F
Fixed temperature 165 °F
Fixed temperature 175 °F
Fixed temperature 135 °F + Rate of Rise (RoR) 15 °F
Fixed temperature 175 °F + Rate of Rise (RoR) 15 °F
Fixed temperature 135 °F + Rate of Rise (RoR) 20 °F
Fixed temperature 175 °F + Rate of Rise (RoR) 20 °F

OOHC941  Selectable  Alarm  Threshold  Setting
Profiles

2.50 % / ft Threshold
3.00 % / ft Threshold
See also section REPLACEMENT OF A DETECTOR IN
AN EXISTING SYSTEM

ELECTRICAL

Supply voltage: 13…32 VDC
Maximum alarm current: 750 µA
Maximum standby current: 430 µA

Refer  to  the  panel  Installation,  Operation  and
Maintenance Manual for maximum line resistance of the
loop card.

WIRING

Detector  bases  for  Model  OOHC941  should  be
connected as shown in Figure 2 and 3.
The  OOHC941  supports  two  operation  modes:  polarity
insensitive mode and isolator mode. The Detector can be
wired for either mode (refer to Figure 2 and 3). During
the isolator mode, the built-in dual isolators will work at
both sides of the Detector to isolate the line short in front
or behind the module.
When the  OOHC941  is  wired  in  polarity  insensitive
mode, Line -6 and -5 can be either line of the loop.
When  the  OOHC941  is  wired  for  Isolator  mode,  the
positive  line  needs  to  be  connected  to  1b  and  the
negative  line  to  6.  The  next  device  needs  to  be
connected to 1b and 5.
The Line Isolator is located between connector 6 and 5.

NOTICE

Ensure that the panel supports Isolator mode for
the OOHC941 product version 30.
Isolator mode must not be used with a
OOHC941, product version <30. You will find the
product version number on the detector label.

DETECTOR MOUNTING

The  recommended  orientation  of  the  detector  for  wall
mounting  is  shown  in  Figure  4.  To  ensure  proper
installation  of  the  detector  head  into  the  base,  be  sure
the wires are properly dressed at installation:

·

  Position all wires flat against the base.

·

  Take up all slack in the outlet box

·

  Route wires away from connector terminals.

Smoke detectors are not to be used with detector guards
unless  the  combination  has been  evaluated  and  found
suitable for that purpose. UL listed with STI Mechanical
Protection  Guard  Model:  STI-9604  (see  www.STI-
USA.com for details).

TO INSTALL DETECTOR HEAD:

Rotate detector counterclockwise while gently pressing
on it until the detector seats fully into base.
Then rotate the detector clockwise until it stops and locks
in  place.  Insert  optional  locking  screw  (Order  Model
LK-11).

TO REMOVE DETECTOR HEAD:

·

Loosen  locking  screw,  if  installed.  Then  rotate  the
detector counterclockwise until stop is reached.

·

  Pull detector out of base.

S54320-F8-A2

OOHC941

30

Содержание OOHC941

Страница 1: ...datory to closely follow the installation drawings In all installations place the detector on the ceiling a minimum of 6 inches from a side wall or on a wall 12 inches from the ceiling For CO gas detection applications follow detector installation requirements in NFPA 72 for Installation of Carbon Monoxide Detection and Warning Equipment For thermal detection use the matrix below Spacing Feet Temp...

Страница 2: ... can also be installed in duct applications between 0 and 4000 ft min For duct installations follow detector installation requirements in NFPA 90A Chapter for Special Ceiling Construction Factors When the detectors employ a fixed temperature rating of 165 F 74 C or less they are intended for a maximum installation temperature of 100 F 38 C LED INDICATOR OPERATION The Model OOHC941 contains an LED ...

Страница 3: ...op When the OOHC941 is wired for Isolator mode the positive line needs to be connected to 1b and the negative line to 6 The next device needs to be connected to 1b and 5 The Line Isolator is located between connector 6 and 5 NOTICE Ensure that the panel supports Isolator mode for the OOHC941 product version 30 Isolator mode must not be used with a OOHC941 product version 30 You will find the produ...

Страница 4: ...mitory Airborne dust and temperature changes living quarters Cooking fumes smoking and steam Utility Room Transformer room normal to somewhat dirty environment heat from running equipment Lobby Relatively clean area temperature changes cellular phones some outside particulate Office Reasonably clean climate controlled atmosphere Hotel Life safety some temperature swings steam smoking and cooking p...

Страница 5: ...TIBLE CONTROL UNIT OR PREVIOUS ADDRESSABLE DEVICE OPTIONAL REMOTE ALARM INDICATOR MODELS 8727W 8727C RL HW RL HC TO NEXT BASE TO NEXT BASE DO NOT USE AN END OF LINE DEVICE DETECTOR BASE MODEL DB 11 DB 11E LINE 1 LINE 2 5 6 1a TB1 TB3 TB2 1b 5 6 1a 1b The relay contacts are shown after System reset which represents the non alarm condition OOHC941 is a polarity insensitive detector Line 1 and Line 2...

Страница 6: ...ensitivity and cause CO sensor troubles This test is simply used to ensure that smoke can enter the sensing chamber and alarm the control panel when the detector reaches the programmed obscuration concentration level CAUTION DO NOT use any test gas other than the one mentioned above as compatibility to the CO sensor cannot be assured CO DETECTOR FUNCTIONAL TEST CO TEST GAS The fire control panel m...

Страница 7: ...pecial applications setting incorporates a pre alarm and sensitive alarm levels to provide a Very Early Waring Fire Detection VEWFD alarm level for applications to avoid business disruption Typical suitable applications for the special applications Telecommunications application profile include Telecommunications Data Centers IT rooms Clean Rooms Laboratories and any clean environment Applications...

Страница 8: ...equipment in accordance with installation instructions manual Read the following information This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules...

Отзывы: