PRE-INSTALLATION

Rotary Address Switches

 - Set the board address for each OCM-16 using both of

the ten-position rotary switches located on the board (See Figure 2). Each of these
addresses must be a sub-address of the NIC-C and must be the same as the ad-
dresses assigned in the Zeus Programming Tool.

S1/S2 LED, Incandescent/Relay Select Switches

•

When LEDs are used, open corresponding dipswitches on S1 and S2 (Refer
to OCM-16 Switches Table) to provide a current limiting resistor of 2.7K
ohms to each LED.

•

When incandescent lamps or relays are used, close corresponding
dipswitches on S1 and S2 (Refer to OCM-16 Switches Table) to bypass the
limiting resistors.

S

E

H

C

T

I

W

S

6

1

-

M

C

O

1

B

T

1

S

h

c

ti

w

S

1

B

T

2

S

h

c

ti

w

S

1

1

-

1

S

9

1

-

2

S

2

2

-

1

S

0

1

2

-

2

S

3

3

-

1

S

1

1

3

-

2

S

4

4

-

1

S

2

1

4

-

2

S

5

5

-

1

S

3

1

5

-

2

S

6

6

-

1

S

4

1

6

-

2

S

7

7

-

1

S

5

1

7

-

2

S

8

8

-

1

S

6

1

8

-

2

S

INSTALLATION

An OCM-16 may be installed in a REMBOX. When using REMBOX 2 or 4, mount the
OCM-16 in one module space on a REMBOX2-MP, P/N 500-634211 or REMBOX4-MP,
P/N 500-634212 using the four screws provided. (Refer to REMBOX2-MP/REMBOX4-
MP Installation Instructions, P/N 315-034211.) Up to 4 OCM-16s will fit in a
REMBOX2; up to 8 OCM-16s will fit in a REMBOX4.

WIRING

Disconnect BATTERY and AC prior to working on equipment.

•

Each OCM-16 module is a node in the CAN bus.

•

The OCM-16 can be installed with or without an RNI. Connect 24V and
CAN bus as shown in Figures 2 and 3.

•

Up to 99 CAN modules, in any combination, can be connected to the CAN
bus of each NIC-C.

•

Each OCM-16 module is shipped with one CCS cable.

•

Cable connections for OCM-16 modules are shown in the following table:

Содержание OCM-16

Страница 1: ...ed by messages received from the NIC C over the CAN A CAN message can activate any or all of the 16 outputs to drive LEDs incandescent 24 Volt lamps or relays Whenever any of the outputs is activated LEDs lamps or relays ON the local audible if installed will sound until it is acknowledged by shorting position 19 and 20 onTB2 If the outputs are deactivated before the alarm local audible is acknowl...

Страница 2: ... S h c t i w S 1 B T 2 S h c t i w S 1 1 1 S 9 1 2 S 2 2 1 S 0 1 2 2 S 3 3 1 S 1 1 3 2 S 4 4 1 S 2 1 4 2 S 5 5 1 S 3 1 5 2 S 6 6 1 S 4 1 6 2 S 7 7 1 S 5 1 7 2 S 8 8 1 S 6 1 8 2 S INSTALLATION An OCM 16 may be installed in a REMBOX When using REMBOX 2 or 4 mount the OCM 16 in one module space on a REMBOX2 MP P N 500 634211 or REMBOX4 MP P N 500 634212 using the four screws provided Refer to REMBOX2...

Страница 3: ...USHBUTTON UL 864 LISTED 24VDC AUDIBLE 50mA MAX UL 864 LISTED UNSUPERVISED UNSUPERVISED ACK ALARM CAN CAN SHIELD SHIELD 24 V 24 V RET USE UP TO 16 LED INCANDESCENT IN ANY COMBINATION UNSUPERVISED RELAY CORRESPONDING DIPSWITCH ON S1 S2 MUST BE SET TO OFF FOR LEDs 24VDC RELAY COIL TB3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 34 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 ON ON 1 5 3 ...

Страница 4: ...9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 1 5 3 7 2 6 4 8 S2 1 5 3 7 2 6 4 8 S1 1 5 3 7 2 6 4 8 S2 1 5 3 7 2 6 4 8 S1 1 5 3 7 2 6 4 8 S2 ...

Отзывы: