Siemens OCM-16 Скачать руководство пользователя страница 1

Siemens Building Technologies

Fire Safety

P/N 315-033150-3

Model OCM-16

Output Control Module

Installation Instructions

INTRODUCTION

The 

SIEMENS 

Model OCM-16 Output Control Module

is a remotely located, general purpose output module. It
provides sixteen open collector outputs to drive LEDs,
incandescent lamps, or external relays. There is an
additional output for a local audible and two inputs for
momentary lamp test and local audible silence switches.

OPERATION

The OCM-16 is mounted in an enclosure that is re-
motely located from the Main Panel. Communication
between the OCM and the NIC-C is through the Control
Area Network (CAN) bus. Each OCM-16 has two 10
position rotary switches that are used to set the board
address on the CAN which is a sub-address of the
NIC-C. The 16 outputs of the OCM-16 are controlled by
messages received from the NIC-C over the CAN.

A CAN message can activate any or all of the 16 outputs
to drive LEDs, incandescent 24 Volt lamps or relays.

Whenever any of the outputs is activated, (LEDs, lamps
or relays ON) the local audible (if installed) will sound
until it is acknowledged by shorting position 19 and 20
on TB2. If the outputs are deactivated before the alarm
(local audible) is acknowledged, the alarm (local
audible) will cease to sound.

By shorting terminals 17 and 18, all LEDs or lamps will
turn on to confirm that they are working and automati-
cally will return to their normal state after a few sec-
onds. Both the lamp test and local audible silence
switch on multiple OCM-16s can be connected to a
single switch, one for each function. A single audible
can also be used with multiple OCM-16s.

Figure 1

OCM-16 Output Control

Module

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

12

3

4 5 6 7

8

90

12

3

4 5 6 7

8

90

S1

1

5

3

7

2

6

4

8

S2

TB2

TB1

P2

P3

TB3

1

5

3

7

2

6

4

8

OCM-16

Содержание OCM-16

Страница 1: ...ed by messages received from the NIC C over the CAN A CAN message can activate any or all of the 16 outputs to drive LEDs incandescent 24 Volt lamps or relays Whenever any of the outputs is activated LEDs lamps or relays ON the local audible if installed will sound until it is acknowledged by shorting position 19 and 20 onTB2 If the outputs are deactivated before the alarm local audible is acknowl...

Страница 2: ... S h c t i w S 1 B T 2 S h c t i w S 1 1 1 S 9 1 2 S 2 2 1 S 0 1 2 2 S 3 3 1 S 1 1 3 2 S 4 4 1 S 2 1 4 2 S 5 5 1 S 3 1 5 2 S 6 6 1 S 4 1 6 2 S 7 7 1 S 5 1 7 2 S 8 8 1 S 6 1 8 2 S INSTALLATION An OCM 16 may be installed in a REMBOX When using REMBOX 2 or 4 mount the OCM 16 in one module space on a REMBOX2 MP P N 500 634211 or REMBOX4 MP P N 500 634212 using the four screws provided Refer to REMBOX2...

Страница 3: ...USHBUTTON UL 864 LISTED 24VDC AUDIBLE 50mA MAX UL 864 LISTED UNSUPERVISED UNSUPERVISED ACK ALARM CAN CAN SHIELD SHIELD 24 V 24 V RET USE UP TO 16 LED INCANDESCENT IN ANY COMBINATION UNSUPERVISED RELAY CORRESPONDING DIPSWITCH ON S1 S2 MUST BE SET TO OFF FOR LEDs 24VDC RELAY COIL TB3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 34 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 ON ON 1 5 3 ...

Страница 4: ...9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 1 5 3 7 2 6 4 8 S2 1 5 3 7 2 6 4 8 S1 1 5 3 7 2 6 4 8 S2 1 5 3 7 2 6 4 8 S1 1 5 3 7 2 6 4 8 S2 ...

Отзывы: