Connect external components
Fire brigade call station (AT) PT2002-A1
7
106 | 121
A6V11940317_en--_a
7.4.8 Logic outputs
The PT2002-A1 provides 4 logic outputs. They are open collector transistors
switching to GND.
The 4 logic outputs can be used to switch lamps, relays or other devices with a
current draw of max. 200mA.
The output can be powered with the DC 10 V provided on pin 12 of the connector,
or with a voltage of max. DC 36 V.
The logic output 1 and 2 are occupied by the PT2002-A1.
Logic outputs connector - 'CN3'
Pin
Description
Remark
1
Analog input 1
The analog control input cannot be used as
the logic output.
2
Analog input 2
The analog control input cannot be used as
the logic output.
3
Analog input 3
The analog control input cannot be used as
the logic output.
4
Analog input 4
The analog control input cannot be used as
the logic output.
5
Analog input 1
The analog control input cannot be used as
the logic output.
6
Analog input 2
The analog control input cannot be used as
the logic output.
7
Logic output 1
Occupied by the PT2002-A1
8
Logic output 2
Occupied by the PT2002-A1
9
Logic output 3
-
10
Logic output 4
-
11
GND
-
12
10 V
-
Table 87: PT2002-A1 logic outputs connector - 'CN3'