Install internal components
System operating unit PT1001-A1
6
68 | 121
A6V11940317_en--_a
6.1.4 Connect DC 24 V power supply
The PT1001-A1 provides one DC 24 V power supply connector ('X1').
DC 24 V power supply connector - 'X1'
Pin
Description
Remark
1
DC 24 V
-
2
DC 0 V
-
Table 35: PT1001-A1 DC 24 V power supply connector - 'X1'
6.1.5 Connect 'PACE-Bus' (RS485)
The PT1001-A1 provides one 'PACE-Bus' (RS485) connector ('X2').
'PACE-Bus' (RS485) connector - 'X2'
Pin
Description
Remark
1
D-
RS485 data -
2
D+
RS485 data +
3
GND
GND reference voltage
Table 36: PT1001-A1 'PACE-Bus' (RS485) connector - 'X2'
6.1.6 Logic control outputs
The PT1001-A1 provides 4 logic control outputs on the connector 'X3'.
The logic control outputs are used to activate LEDs or communicate a status
change of the system.
The logic control outputs are open collector outputs which switch to IO-GND. A
power source is required to use the outputs.
● Max. current per output is 200 mA.
● Max. current on internal 12 V power source is 250 mA.
Logic control outputs connector - 'X3'
Pin
Description
Remark
1
O1
-
2
O2
-
3
O3
-
4
O4
-
5
IO-GND
IO-GND not connected to GND
6
12 V
12 V reference voltage
Table 37: PT1001-A1 logic control outputs connector - 'X3'
For use of logic control outputs, see