NK8000 network planning
83
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
the network depends on the fibre characteristics and the type of optical transceivers
used (from 2 km with multimode fibre up to 95 km with G.652/G.653 fibre).
The following image shows a NK8000 network, which uses an OTN network as
backbone.
Fig. 52 NK8000 network built with OTN as backbone
NK8000 is only one of the applications that can share the OTN network, together with
CCTV-, access control-, and telephony applications (not shown in Fig. 52).
You can find more information about OTN at:
5.4 Shared
network
It is possible to integrate FS NK8000 and management station products into a cus-
tomer’s network, however you need to be aware of/satisfy the following
requirements
:
·
Only Ethernet is supported
·
The DMS PC (in general) supports 10BaseT, 100BaseT, and so on, but this de-
pends on the network card in the PC
·
NK823x supports 10BaseT and 100BaseT, half-duplex and full-duplex mode, auto-
negotiation and auto crossover
·
Each management station-PC and each NK82xx needs a fixed IP-Address (NO
DHCP)
·
An RJ45 Ethernet outlet must be close to the facility