background image

2

Figure 1
Original NCC Software Key Placement

1

2

3

4

5

6

1
2
3
4
5
6
7
8

See Notes 3 and 4

Flexible Conduit

(User Supplied)

Conduit

AC Main

120 VAC 60Hz

To Parallel Printer

See Notes 3 and 5

SCD19TM or SCD21TM

See Notes 1, 2, 3, 4, and 5

*The COM port on the Main

CPU must be disabled if
NCC-1F is being used.
See Note 13

Computer (rear view)

Junction

Box

(user

supplied)

120 VAC

60 Hz

Monitor

(rear view)

Touch

Interface

Port A

Mouse

Keyboard

Ethernet

COM 2

Elo Touch Screen

Controller Card

See Note 14

Sound

Card

VIDEO

LPT1

(NCC

Key)

LPT

POR

T

2

(NCC

Key)

LPT

POR

T

2

NOTES:

1. NCC-1F card is installed in a 16-bit ISA

slot and is set for COM2.

2. Connect the keyboard and mouse to the

computer's keyboard and mouse ports
following the computer's installation
instructions.

3. NFPA 72 Proprietary and Local System

installation requires that the computer,
monitor, and printer be UL rated for fire
(

SIEMENS

 Models SCD550, SCD550T,

SCD19M, SCD19TM, SCD21M,
SDC21TM and PAL-1, respectively).

4. The computer is supervised for power

and connection to MXL.

5. The printer is supervised for AC, on/off

line, paper out, paper jam, and connec-
tion to the computer by NCCNT-G
software at the computer.

6. All circuits are power limited.

7. Cable must be in rigid conduit and cannot

leave the room.

8. Shielded cable is not recommended.

9. Power limited to NFPA 70 per NEC 760.

10. Maximum voltage: 24V peak to peak.

11. Maximum current: 20mA per circuit.

12. LPT2 has software key.

13. The COM Port on the Main CPU is

disabled. The Serial Port on the Serial
Parallel Adapter card takes on the
identification of COM1. The NCC-1F card
is identified as COM2.

14. If you are using model SCD-19M, the

touch screen controller card is not
installed.

15. Pin 1 & 2 of the LPT2 board can be wired

to a TRI module to monitor the status of
the computer's CPU.

Figure 2
Connecting The Upgrade NCC Software Key To The Existing NCC Software Key

Содержание NCC-G16

Страница 1: ... NCC 3G 48 node graphics NCC 4T UK allows an existing NCC 4T 64 node text to upgrade to a NCC 4G 64 node graphics NCC GL1 allows an existing NCC GL system to upgrade to a NCC 1G 16 node graphics All FireFinder NCC upgrade kits are compatible with both the NCC OS 2 version and NCC NT version The minimum NCC software revision required to recognize the NCC software upgrade keys is 2 23 for the OS 2 v...

Страница 2: ...puter monitor and printer be UL rated for fire SIEMENS Models SCD550 SCD550T SCD19M SCD19TM SCD21M SDC21TM and PAL 1 respectively 4 The computer is supervised for power and connection to MXL 5 The printer is supervised for AC on off line paper out paper jam and connec tion to the computer by NCCNT G software at the computer 6 All circuits are power limited 7 Cable must be in rigid conduit and cann...

Страница 3: ... the following window Figure 5 C WINNT System32 CMD exe Screen In this window you will see the statement If you do not want to restart the NCC hit CTRL C Press the Ctrl key and the C key simultaneously The following statement appears Terminate batch job Y N as shown in the following window Figure 6 Terminate Batch Job Y N Screen Choose Y and press ENTER From the Windows NT Start Button click on Sh...

Страница 4: ...able the graphics display option To enable the graphics display option hit the MORE button on the main display then hit the SETUP button From the system setup notebook hit the DISPLAY tab You will see the enable graphics display option Click in the adjacent box so that a check mark appears next to the option This check mark assures that the option has been activated Once activated hit the SAVE but...

Отзывы: