Technical Manual

Switch/Dimming Actuator
N526E02

5WG1 526-1EB02

June 2015 / Page 2

B1

C2

C3

B2

C1

D 1.1

D1

( 9 ,5 mm )

E1.1

E1.2

E1

  3 / 8 “

Location and Function of the Display
and Control Elements

0

A4

A3

A2

A1

A5

A6

A1

LED for indicating normal operating mode (LED off)
and addressing mode (LED on); upon receiving the
physical address the device automatically returns to
normal operating mode

A2

Learning button for switching between normal oper-
ating mode and addressing mode

A3

bus connection block, screw-less

A4

screw terminals for connecting the control circuits

A5

Slide switches for manual operation and for displaying
the switching position per channel.
Slide in upper position: relay contact open (OFF)
Slide in lower position: relay contact closed (ON)

A6

mains connection blocks (screw terminals) for
connecting load circuits

Important note:
Manual operation is for emergency operation only and not af-
fecting the application program. No telegram is sent on the
bus, and the new switching status is unknown to the soft-
ware.
At bus voltage failure / recovery a previously manually oper-
ated relay will also be set automatically to the configured po-
sition.

Installation Instructions

The device may be used for permanent interior installations
in dry locations within distribution boards or small casings
with DIN rail EN 60715-TH35-7,5.
This equipment is intended for field installation within the
enclosure of another product.

Typical circuit

N

PE

L

+

-

26

3

+

-

N

PE

L

+

-

26

+

-

N

PE

L

+

-

26

+

-

Switching/Dimming
Actuator N 526E

N

PE

L

Load circuit
mains voltage

L1 PE

N

ECG Dynamic

+

-

26

25

fluorescent lamp

+

-

Channel A

bu

s

co

up

li

ng

un

it

C

on

tr

ol

D

C

0.

..1

0

V

S

up

pl

y

m

ai

ns

vo

lta

ge

S

w

itc

hi

ng

m

ai

ns

vo

lta

ge

D

im

m

in

g

D

C

0.

..1

0

V

in

st

ab

us

E

IB

2

1

L

L

Mounting

General description
The N-system DIN-rail device can be installed in the
instabus EIB lighting control panel, surface or flush mounted,
or to any DIN rail in distribution boards, surface or flush
mounted,complying with EN 60715-TH35-7,5 that has a da-
ta rail installed.
The connection to the bus line is established by clicking the
device onto the DIN-rail (with a data rail installed). Take care
that the type plates of all devices on a DIN-rail can be read in
the same direction, guaranteeing the devices are polarised
correctly.

Mounting the Power Supply unit N 125 to a DIN-rail
• Slide the DIN-rail device (B1) onto the DIN-rail (B2) and
• swivel back the DIN-rail device until the slide clicks into
  place audibly.

Dismounting DIN-rail devices
• Remove all connected wires,
• press down the slide (C3) with a screw-driver and
• swivel the DIN-rail device (C1) from the DIN-rail (C2).

Connection to the bus without data rail
If the connection is established via bus connection block
(data rail not installed) the data rail connection system has to
be covered with the enclosed insulation hood after removing
the guiding hood e.g. with a screw driver to guarantee a suf-
ficient insulation from the DIN rail.

Removing the guiding top

-

The guiding top (D3) surrounds the contact system (D2)
on the back side of the device (D1).

-

Insert the screw driver between the DIN-rail device (D1)
and the guiding hood (D3) and remove the guiding hood.

Inserting the insulation top

-

Put the insulation top (D4) onto the contact system and
click it into place by a slight pressure.

Wiring

Connecting mains
• Mains is connected via screwless plug-in terminals (D1).
• Remove approx. 3/8" (9,5mm) of insulation from the wire
  (D1.1) and plug it into the terminal (D1).

Disconnect mains
• Press the terminal lock (E1.2) with a screw-driver and
• remove the wire (E1.1) from the terminal (E1).

E1

E2

5 mm

E1

E2

Slipping on of the safety extra low voltage block

-

slip the connection block  onto the guide slot and

-

press the connection block down to the stop

Connecting the safety extra low voltage block

-

The  connection block (E1) can be used with single core
conductors Ø 0,6 ... 0,8 mm.

-

Remove approx. 5 mm of insulation from the conductor
(E2) and plug it into the connection block (E1) (red = +,
black = -).

Disconnecting the safety extra low voltage block

-

Unplug the connection block (E1) and remove the bus ca-
ble conductor (E2) while simultaneously wiggling it.

D3

D1

D2

D2

D4 D1

WARNING
WARNING

Hazardous voltage. Can cause death, or serious injury or property damage.
Disconnect and lock off power before installing or working on the device.
Risk of Electric Shock – More than one disconnect switch may be required to de-
energize the equipment before servicing.

The device must not be opened.
A faulty device should be returned to the local Siemens sales office or distributor.

The device must be mounted and commissioned by a factory trained person.
The prevailing safety rules must be observed!
Mount in dry locations only!