background image

Turn off and lock out all power supplying this device before 
working on this device.
Replace all covers before power supplying this device is 
turned on.

Couper l'alimentation de l'appareil et barrer avant de 
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.

Tensión peligrosa.
Puede causar la muerte o lesiones graves.

Tension dangereuse.
Danger de mort ou risque de blessures graves.

Hazardous Voltage.
Will cause death or serious injury.

Desenergice totalmente antes de instalar o darle servicio. 
Reemplace todas las barreras y cubiertas antes de 
energizar el interruptor.

Turn off and lock out all power supplying this device before 
working on this device.
Replace all covers before power supplying this device is 
turned on.

Couper l'alimentation de l'appareil et barrer avant de 
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.

Tensión peligrosa.
Puede causar la muerte o lesiones graves.

Tension dangereuse.
Danger de mort ou risque de blessures graves.

Hazardous Voltage.
Will cause death or serious injury.

Desenergice totalmente antes de instalar o darle servicio. 
Reemplace todas las barreras y cubiertas antes de 
energizar el interruptor.

1.

Prepare circuit breaker enclosure for neutral installation.

Turn OFF and lock out all power supplying this device before working on the device.

Turn OFF the circuit breaker.

2.

Mount neutral as shown below.

Torque to 27 lb-ins.

Bonding

When bonded neutral is required:

Insert Neutral Bonding Screw into bonding location shown

Torque Neutral Bonding Screw to 27 lb-ins

Apply Service Disconnect Label to cover if applicable

Bonding Location

Subject to change without prior notice                                                                                       

© Siemens Industry Inc. 2015

Siemens Industry Inc., Norcross, GA 30092

Technical Support:                  

Toll Free: 1-800-241-4453

Internet: www.usa.siemens.com/powerdistribution

I.L. No. 506199A00

2 /  2

Wire Range

Main Neutral

6 AWG – 350 kcmil CU / AL

Service Ground

14 AWG –1/0 AWG  CU / AL