Turn off and lock out all power supplying this device before
working on this device.
Replace all covers before power supplying this device is
turned on.
Couper l'alimentation de l'appareil et barrer avant de
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Hazardous Voltage.
Will cause death or serious injury.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
Turn off and lock out all power supplying this device before
working on this device.
Replace all covers before power supplying this device is
turned on.
Couper l'alimentation de l'appareil et barrer avant de
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Hazardous Voltage.
Will cause death or serious injury.
Desenergice totalmente antes de instalar o darle servicio.
Reemplace todas las barreras y cubiertas antes de
energizar el interruptor.
1.
Prepare circuit breaker enclosure for neutral installation.
Turn OFF and lock out all power supplying this device before working on the device.
Turn OFF the circuit breaker.
2.
Mount neutral as shown below.
Torque to 27 lb-ins.
Bonding
When bonded neutral is required:
•
Insert Neutral Bonding Screw into bonding location shown
•
Torque Neutral Bonding Screw to 27 lb-ins
•
Apply Service Disconnect Label to cover if applicable
Bonding Location
Subject to change without prior notice
© Siemens Industry Inc. 2015
Siemens Industry Inc., Norcross, GA 30092
Technical Support:
Toll Free: 1-800-241-4453
Internet: www.usa.siemens.com/powerdistribution
I.L. No. 506199A00
2 / 2
Wire Range
Main Neutral
6 AWG – 350 kcmil CU / AL
Service Ground
14 AWG –1/0 AWG CU / AL