background image

 

GAMMA 

instabus

 

Technical product information 

December 2009 

N 562/11 Switching actuator, main module

 5WG1 

562-1AB11 

3x AC 230/400 V, 10 AX, C-load, load-check 

 

 

Siemens AG 

N 562/11, 6 pages 

Technical manual 

Industry Sector, Building Technologies 

Low Voltage Distribution 

© Siemens AG 2009 

Update: http://www.siemens.com/gamma 

P.O. Box 100953, D-93009 Regensburg 

Subject to change without further notice 

 

 

2.4.3.4/1 

Product and functional description

 

 

 

The switching actuator main module N 562/11 is a DIN-

rail mounted device with N-system dimensions. It can 

switch three groups of electrical consumers, independent 

of each other, via its three relay contact outputs. The bus 

is connected via a bus terminal block. The actuator elec-

tronics are supplied via the bus voltage. 

 

Connection of switching actuator submodules 

A switching actuator submodule N 562/21 or N 512/21 

(see device B in figure 1) can be connected to the switch-

ing actuator main module N 562/11 (see device A in 

figure 1) via the 6-pin interface with a special jumper. A 

further switching actuator submodule can be connected 

likewise to a previous switching actuator submodule. In 

total up to 4 switching actuator submodules N 562/21 or 

N 512/21 can be connected in series to a switching ac-

tuator main module N 562/11, so that a main module, if 

need be, can be extended simply from a 3-fold to a 6-, 9-, 

12- or 15-fold switching actuator and thus be matched 

flexibly to the size and number of loads to be switched. 

 

LED display 

Five green light emitting diodes (LED) on the top of the 

main module (see figure 2, A5) indicate which module is 

selected (LED = ON). A module can be selected by tap-

ping the pushbutton “Direct mode” (see figure 2, A6) 

once or several times until the LED of the desired module 

A to E illuminates. If any of the green LED A to E is flash-

ing a fault was detected at this module. For example, this 

is the case if more modules are configured than are actu-

ally connected or if the configured module type does not 

correspond with the module type actually connected or if 

a module is detected as faulty. 

 

Bus mode / Direct mode 

The Direct mode pushbutton (see figure 2, A6) with an 

integrated yellow LED may be used to toggle between 

Bus mode and Direct mode. If this pushbutton is pressed 

briefly, the associated green LED indicates for 30 seconds 

which of the modules A to E (see figure 2, A5) was se-

lected last and the switching state of the corresponding 

outputs is indicated by the red LED integrated in buttons 

1 to 3 (see figure 2, A9; relay contact closed: LED = ON, 

contact open: LED = OFF).  

However, if the button to switch on Direct mode is held 

down for at least 3 seconds, then the yellow LED to indi-

cate Direct mode turns on permanently. In Direct mode, 

each output of the currently selected module can be 

switched via the allocated pushbutton on the top of the 

main module through a toggling function: a first press on 

the pushbutton switches the output on if it is switched 

off, a second press switches it off again. The switching 

state of the output is indicated by the red LED incorpo-

rated in the pushbutton. (Note: Pushbuttons 4 to 6 and 

the incorporated LED are not used in the N 562/11.) To 

change the switching state of the outputs of another 

module, this module must be selected first. To do this, 

you must briefly press the Direct mode pushbutton sev-

eral times until the LED of the desired module A to E 

illuminates. Modules that are connected but not yet set 

up as connected cannot be selected. 

A parameter determines whether Direct mode can be 

switched on permanently or for a limited period. The 

factory default setting limits the Direct mode period to 

15 minutes. Each time the pushbutton is pressed the 

timer is reset to 15 minutes. After the period has elapsed 

without a further key press, Direct mode is switched off 

automatically and Bus mode is re-enabled accordingly (if 

communication via the bus is possible). Alternatively, 

Direct mode can be left at any time by pressing the Direct 

mode pushbutton for at least 3 seconds. Then the yellow 

LED for indicating Direct mode turns off and the actuator 

operates in Bus mode. In Bus mode, pressing the 

pushbutton for direct switching of an output off or on 

does not work. If Direct mode is active, switching and 

scene recall commands received via the bus are buffered 

and automatically executed after switching back to Bus 

mode. 

 

Behavior in case of mains failure / recovery 

Because the actuator electronics are fed from the bus, a 
mains failure then leads solely to a failure of the actuator 
function if the bus voltage also fails as the result of a 
mains failure. However, it can be set for each actuator 
output individually which switching state it is to assume 
on a bus voltage failure and after the bus voltage recov-
ery: as before bus voltage failure, ON or OFF. 

Содержание N 562/11

Страница 1: ...r 30 seconds which of the modules A to E see figure 2 A5 was se lected last and the switching state of the corresponding outputs is indicated by the red LED integrated in buttons 1 to 3 see figure 2 A9 relay contact closed LED ON contact open LED OFF However if the button to switch on Direct mode is held down for at least 3 seconds then the yellow LED to indi cate Direct mode turns on permanently ...

Страница 2: ...peed con trol conversion of a valve setting preset as a percentage into a pulse width modulated switching command thermal drive control a switching cycle and runtime totalization with threshold monitoring for each output and an integrated 8 bit scene control in which each output can be incorporated into up to 8 scenes To load the application program the Engineering Tool Software ETS is required as...

Страница 3: ...ing between normal mode addressing mode 1 pushbutton for toggling between bus mode direct mode 2x 3 pushbuttons in 2 rows for direct operation toggling of 3 actuator outputs per row independent of the bus Display elements 1 red LED for checking the bus voltage and for display ing normal mode addressing mode 5 green LED for display of the selected module 1 yellow LED for displaying direct mode bus ...

Страница 4: ... A4 Jack for connection of a switching actuator sub module A5 LED to indicate the selected device A6 Pushbutton to toggle between Bus Direct mode A7 LED to indicate Direct mode On A8 Pushbutton for direct operation of outputs 1 3 A9 LED to indicate whether the corresponding output is switched on or off A10 Without function A11 Without function A12 Screw type terminals of outputs 1 3 Installation a...

Страница 5: ... notice 2 4 3 4 5 General notes The operating instructions must be handed over to the client A faulty device shall be sent with a Return Good Note for Service provided by the appropriate Siemens sales office to the following address SIEMENS AG Siemensstr 10 D 93055 Regensburg If you have further questions concerning the product please contact our technical support 49 0 180 50 50 222 0 14 min from ...

Страница 6: ...62 1AB11 3x AC 230 400 V 10 AX C load load check Technical manual N 562 11 6 pages Siemens AG Industry Sector Building Technologies Update http www siemens com gamma Siemens AG 2009 Low Voltage Distribution Subject to change without further notice P O Box 100953 D 93009 Regensburg 2 4 3 4 6 Space for notes ...

Отзывы: