System Messages
C-8
MP270 Equipment Manual
Release 01/99
Remedy
Effect/Cause
Number
150000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interface.
The system is overloaded.
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
150001
Connection is re-established because the cause of
the interruption has been eliminated.
–
160000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interfacet.
The system is overloaded.
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
160001
Connection is re-established because the cause of
the interruption has been eliminated.
–
170000
1)
S7
diagnostics messages are not displayed because
it is not possible to logon to the S7
diagnostics with
this unit. The service program is not supported.
–
170001
1)
The S7 diagnostics buffer cannot be displayed
because communication with the PLC has been
switched off.
Switch the PLC online.
170002
1)
The S7
diagnostics buffer cannot be displayed
because reading in the diagnostics buffer (SZL) was
terminated due to an error.
–
170003
1)
The display of an S7
diagnostics message is not
possible. An internal error %2 has been reported.
–
170004
1)
The display of an S7
diagnostics message is not
possible. An internal error with error class %2, error
number %3 has been reported.
–
170007
1)
It is not possible to read in the S7
diagnostics buffer
(SZL) because it was terminated with an internal error
with error class %2 and error code %3.
–
180000
A component/OCX receives configuration data with a
version identification which is not supported.
Install a newer component.
190000
It is possible that the tag will not be updated.
–
190001
The tag is updated following an error status after the
cause of the last error state has been eliminated
(return to normal operation).
–
190002
The tag is not updated because communication to the
PLC has been switched off.
Switch on communication via the
function “Set Online”.
190004
The tag is not updated because the configured
address is not available for this tag .
Check the configuration.
190005
The tag is not updated because the configured PLC
type does not exist for this tag .
Check the configuration.
Содержание Multi Panel MP270 SIMATIC HMI
Страница 8: ...Preface vi MP270Equipment Manual Release01 99 ...
Страница 18: ...Functionality 2 4 MP270EquipmentManual Release01 99 ...
Страница 36: ...MP270 Operation 4 14 MP270Equipment Manual Release01 99 ...
Страница 64: ...System Settings 6 8 MP270Equipment Manual Release01 99 ...
Страница 82: ...Unit Description 8 8 MP270Equipment Manual Release01 99 ...
Страница 90: ...Maintenance Upkeep 10 4 MP270Equipment Manual Release01 99 ...
Страница 92: ...APPENDICES J 2 MP270Equipment Manual Release01 99 ...
Страница 98: ...Technical Data A 6 MP270Equipment Manual Release01 99 ...
Страница 114: ...System Messages C 14 MP270Equipment Manual Release01 99 ...
Страница 144: ...Index Index 8 MP270Equipment Manual Release01 99 ...