Configuring the MT8001
45
Building Technologies
048_DMS_MT8001_ICC_MP4.20_A6V10096181_a_en.doc
Fire Safety & Security Products
06.2009
5.4.4
Defining event behaviour – Treatment instructions/information
Associate any special procedures with its corresponding zone or device
There may be some rooms or situations where a special procedure or information
should be provided in addition to that in the default procedure. For example, pro-
viding the operator with special instructions, or providing a notification that hazard-
ous or explosive materials are contained in an area where an alarm is occurring.
Once you have placed these bitmaps in the XMLData\Instructions folder, you can
associate them with the corresponding zones or elements.
To associate a special procedure or additional information with its corresponding
object, do the following:
1.
Select the object that should have the special procedure associated with it.
2.
Select the property that the procedure applies to. (See Fig. 43, B.)
3.
Select the instruction “bitmap” from the
Instruction File Name
drop-down list in
the
Field Point Data
4.
Repeat steps 2 and 3 for each property that the procedure should apply to.
Fig. 43 Associate the procedure with the device
A
Select the device (e.g.: section, zone, element, etc.).
B
Select the alarm state.
C
Select the Instruction to be associated with the device state.
A
B
C