Auxiliary Switch ASC10.51 switches on or off when a certain 
position is reached. The switching point can lie between 0 to 100%. 

Service Kit

 

If the actuator is inoperative, replace the unit. 

 

Operation 

A zero voltage control signal returns the valve to its normal position.  

In the event of a power failure: 

  SAS61.03U is non-spring return and holds its last position. 

  SAS61.33U returns the valve to its normal spring return position. 

The position output 0 to 10 Vdc signal “U” produces position feedback to the controller. 

Mounting and 
Installation 

 

Figure 1.  Acceptable Mounting Positions. 

Mount the actuator in any position 

except

 with the actuator lower than the valve. 

Figure 1 shows acceptable actuator mounting positions for water applications. The 
recommended mounting position of the actuator for low pressure steam applications is 
between 45° and horizontal.  

Wiring 

  All units using the same control signal must utilize the same neutral reference (G0). 

  Use earth ground isolating, step-down Class 2 transformers. Do 

not

 use auto 

transformers. 

  Determine supply transformer minimum rating by summing the total equipment on 

circuit. The maximum rating for Class 2 step-down transformers is 100 VA. 

  Do 

not

 power more than 10 actuators with one transformer. 

 

 

WARNING: 

Housing rated for flex conduit only. 

 

 

Содержание MT SAS Series

Страница 1: ...n allows for repositioning Mechanical spring returns the valve to its normal fail safe position in power off conditions SAS61 33U Actuator only Application For use in small to medium HVAC installations with Powermite 599 Series terminal unit valves with a 7 32 inch 5 5 mm stroke requiring a minimum of 90 pounds force 400N They can be used in liquid and low pressure steam service applications Table...

Страница 2: ...t load 1 mA max Z Forced control Resistance 0 to 1000Ω stroke proportional to R Z connected to G Max stroke 100 Z connected to G0 Min stroke 0 Voltage Max 24 Vac to 20 Max 24 Vdc 20 15 Current draw 0 1 mA Functional Operation Running time at 60 Hz 30 seconds Spring return SAS61 33U only 14 seconds Nominal stroke 7 32 inch 5 5 mm Nominal Force 90 lbs 400N Spring return SAS61 33U only Mechanical spr...

Страница 3: ...o 10 Vdc signal U produces position feedback to the controller Mounting and Installation Figure 1 Acceptable Mounting Positions Mount the actuator in any position except with the actuator lower than the valve Figure 1 shows acceptable actuator mounting positions for water applications The recommended mounting position of the actuator for low pressure steam applications is between 45 and horizontal...

Страница 4: ...AC DC 24V 0 to 1000 Ω Figure 2 Terminal Connections WARNING Terminal connection G is 24 Vac HOT not ground CAUTION G0 and G must be properly wired for correct function and full life of the actuator Figure 3 Wiring Diagram The diagram shows all possible connections The application determines which connections are used Start up The valve body normally open or normally closed determines the action of...

Страница 5: ...spective owners 2016 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 USA 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 155 682 Printed in the USA Page 5 Dimensions A B C1 C2 D E Inches 5 9 3 1 0 9 2 8 1 2 0 9 4 8 m...

Отзывы: