UM353-1
Function Blocks
March 2003
3-35
COIL INPUTS 16 CHAN - ETHERNET
COIL INPUTS
CIE_
16-CHAN ETHERNET
C0
Output
C0
CF
Output
CF
IP A D
d
RES
s
(H)
....
nnn.nnn.nnn.nn n
(192.168.0.0)
QS
Output
QS
Ethernet Network
START
ing
C
oi
L
(H)
.. 0000 - 65535
(null)
NO. OF C
oi
L
s
(H)
................ 1 - 16
(1)
MB A D
d
RES
s
(H)
.............. 1 - 255
(1)
P
A
R E S
S
I
D
T A R
F
Y
L
C
L
N O
O
T
A D R E S
B
M
D A T A
T
P
DATA
TYP
e
(H)
............
Coil/InPut
(Coil)
C
U
p
D
ate
RATE
(H)
.............. P2P/Ct
(P2P)
E
T
A
R
D
U
3.2.25 CIE_- Coil Inputs - Ethernet (V3.0)
CIE_ function blocks are available when the
optional Ethernet communication board
installed in the controller. It enables the controller
to obtain Coil data from other stations over the
Ethernet network.
Up to 32 CIE_ blocks are available. Blocks are
assigned in sequence, controller wide, with each
use. Up to 16 Coils can be obtained from a
Modbus device. Each Coil is assigned to block
outputs C0 – CF.
The IP ADRES parameter is used to configure the
IP address of the source Modbus device. The
MB ADRES parameter allows a Modbus address
to be configured. When connecting to other
Siemens MOORE controllers, the Modbus
address is set to 1. In some cases, other Modbus
devices may use a different address or when
going through a Modbus TCP/IP gateway a Modbus network may have multiple devices, each having a unique
address.
The START CL parameter identifies the location of the first Coil. Subsequent Coils, up to 16, can be obtained by
setting the NO OF CL parameter to a value greater than 1. The DATA TYP parameter enables reading of Coils
(Modbus Function Code 01) or Inputs (Modbus Function Code 02). Both are treated the same but the Coil type is
the most common usage. The UD RATE parameter configures the rate at which the block will request data. The
P2P setting will update the data at the rate set by the P2P RATE parameter in the ETHERNET block. The Ct
setting will update the data at the cycle time of the controller.
Output QS indicates the quality of the received data and will go high (1) when the data is bad. This is normally
associated with failure to receive data due to a communication failure or a misconfiguration of the source.
8
Requires Ethernet communications board firmware version 2.0 or later
StockCheck.com
Содержание Moore 353
Страница 2: ...S t o c k C h e c k c o m ...
Страница 14: ...Contents UM353 1 xii March 2003 S t o c k C h e c k c o m ...
Страница 24: ...Introduction UM353 1 March 2003 1 10 S t o c k C h e c k c o m ...
Страница 152: ...LonWorks Communications UM353 1 March 2003 5 4 S t o c k C h e c k c o m ...
Страница 164: ...Network Communications UM353 1 6 12 March 2003 S t o c k C h e c k c o m ...
Страница 246: ...Operation UM353 1 March 2003 9 8 S t o c k C h e c k c o m ...
Страница 254: ...Controller and System Test UM353 1 March 2003 10 8 S t o c k C h e c k c o m ...
Страница 282: ...Circuit Description UM353 1 March 2003 13 4 S t o c k C h e c k c o m ...
Страница 298: ...Model Designation and Specifications UM353 1 March 2003 14 16 S t o c k C h e c k c o m ...
Страница 302: ...Abbreviations And Acronyms UM353 1 15 2 March 2003 S t o c k C h e c k c o m ...
Страница 304: ...Warranty UM353 1 W 2 March 2003 S t o c k C h e c k c o m ...